Permit Review Detail
Review Status: Requires Resubmit
Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Permit Number - TC-MDP-0624-00752
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2024 | Site Engineering | APPROVED | |||
| 07/19/2024 | Site Zoning | APPROVED | |||
| 07/16/2024 | Fire New Construction | NOT REQUIRED | |||
| 08/30/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/07/2024 | Residential Building | REQUIRES RESUBMIT | Review Comments: 1) The separation distance between Units 5 and 6 is less than the minimum required distance of 6'-0". Each dwelling unit should have an individual 3-foot clear space (including the roof projections) known as the fire separation distance for reducing fire spread to nearby buildings. Portions of buildings placed in a fire separation distance require one-hour fire-resistive construction in compliance with IBC Table 721.1(2). A revision to this permit detailing a one hour fire-resistive rating will be required. Juan Garcia 520-837-6953 |
||
| 07/05/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 07/08/2024 | ROW Engineering Review | REVIEW COMPLETED | No comments |