Permit Number: TC-MDP-0624-00751
Parcel: 140062780

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1

Permit Number - TC-MDP-0624-00751
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2024 Residential Building APPROVED
07/24/2024 Site Engineering APPROVED
07/16/2024 Fire New Construction NOT REQUIRED
07/24/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/12/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-MDP-0624-00751
3573 E NEBRASKA SV. – R-1
New SFR (1st Review)

TRANSMITTAL DATE: July 12, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. The lot coverage calculation is not correct. Review UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, and provide a correct lot coverage calculation. Lot coverage does not include walkways and should be expressed as a percentage of lot coverage not undisturbed area.

2. The required front perimeter yard setback is not correct. Per UDC Article 6.4.5.C.1.a the required setback is 20’-0”.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/05/2024 PDSD Application Completeness Express REVIEW COMPLETED
07/08/2024 ROW Engineering Review REVIEW COMPLETED PIA will cover improvements in the Right of Way