Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-MDP-0623-01136
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/01/2024 Post-Tension Inspection (Deferred Submittal) REQUIRES RESUBMIT Permit Review TC-MDP-0623-01136 • Post-Tension Inspection (Deferred Submittal)

Two of the PT tendon elongations (#11 and 17) are greater than the maximum range. Provide a letter from the EOR stating that is acceptable. Or the EOR shall provide a design fix if necessary.
02/27/2024 PDSD Application Completeness REVIEW COMPLETED