Permit Review Detail
Review Status: Requires Resubmit
Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.2
Permit Number - TC-MDP-0425-00280
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2025 | Site Zoning | APPROVED | |||
| 07/02/2025 | Fire New Construction | NOT REQUIRED | |||
| 07/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/01/2025 | Residential Building | REQUIRES RESUBMIT | TC-MDP-0425-00280 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: Provide a floor plan consistent with the referenced one-bedroom model Accessory Dwelling Unit (TC-MDP-0223-00619) or provide a complete construction plan set for the 762 SF dwelling shown on sheet G1.2 with a new application for a new ADU. Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files. SITE PLAN: 1. Show the upgraded yard pipe size (1”) between meter and SOV, 2093.7. 2. Provide electrical load calculations for determining the service panel size, E3602.2. The plan shows (N) 200 AMP upgrade, but the Utility Note #08 shows a 400 AMP service. If you have any questions, please contact: Ken Van Karsen PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/pdsd |
||
| 07/18/2025 | Site Engineering | REQUIRES RESUBMIT | Permit: TC-MDP-0425-00280 Location: 1621 N PALO VERDE BL Review Date: 7/18/2025 Site Engineering Comments: 1. This project lies within a recognized floodplain and requires a Floodplain Use Permit (FUP). Please start a new FPU at our permit application web page: https://tdc-online.tucsonaz.gov/#/home 2. Site engineering will be unable to approve the associated building permit TC-MDP-0425-00280 until the associated Floodplain Use Permit (FPU) is reviewed and issued. 3. An elevation certificate will be required to complete the FUP application. The base flood elevation for the ADU site is 2454.75 ft which requires a finished floor elevation (FFE) of 2455.75 ft for the Duplex unit. 4. For the resubmitted plans, ensure that the Finished Floor Elevation is notated on the site plans. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 07/01/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 07/14/2025 | ROW Engineering Review | REVIEW COMPLETED | DTM has not comments at this time proposed work not effecting right of way. Any work within the Right of Way will required separate and individual ROW permits for each scope of work that is performed. |