Permit Number: TC-FBB-1224-00204
Parcel: 132131900

Address:
2637 S AYALA ST

Review Status: Requires Resubmit

Review Details: FACTORY BUILT BUILDINGS v.1

Permit Number - TC-FBB-1224-00204
Review Name: FACTORY BUILT BUILDINGS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2025 Commercial Building APPROVED
01/13/2025 Site Zoning APPROVED
01/10/2025 Site Engineering NOT REQUIRED
01/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/10/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-FBB-1224-00204 (2637 S AYALA ST TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide an electrical riser diagram, 2017 NEC 230.9. Notate the grounding and bonding method, 2017 NEC 250.20(B), 250.24, 250.30(A)(4).
2. Indicate if the power connection from TEP to the MSP is underground or overhead.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/26/2024 PDSD Application Completeness Express REVIEW COMPLETED