Permit Number: TC-FBB-1125-00127
Parcel: 116200880

Review Status: Requires Resubmit

Review Details: SHIPPING CONTAINER v.1

Permit Number - TC-FBB-1125-00127
Review Name: SHIPPING CONTAINER v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/08/2025 Commercial Building - Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please indicate the use of each of the Conex structures on the plans, provide a foundation and anchoring system design, with calculations and construction drawings prepared and sealed by an Arizona Registrant that adequately show the scope of work and compliance with the adopted building codes. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Please indicate no utilities to be connected with this permit. Future Electric Sleeve, Water Sleeve and Gas Sleeves are being installed at risk and will require separate(s). Please note underground gas line sleeves are to be installed and vented in accordance with IRC Chapter 24 or IFGC Chapter 4.
3. Please provide a valid address for the parcel where these structures are proposed to be used. IBC 107.1
4. Please indicate the applicable codes used for this project. For example,
2018 International Building Code (IBC)
2018 International Residential Code (IRC)
2018 International Plumbing Code (IPC)
2017 National Electrical Code (NEC)
2024 International Fire Code (IFC)
2018 International Fuel Gas (IFGC)
Local Amendments to Above Codes ( www.tucsonaz.gov/pdsd/building-codes )
5. Please note this submittal was incomplete and further comments are likely with the next review.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
12/07/2025 Design Review - Standard REQUIRES RESUBMIT The property is located within the Rio Nuevo Area (RNA) overlay zone. A complete Design Package will need to be submitted for review by the Design Review Board and staff as a subrecord of this Development Package, following these instructions: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf, and demonstrating compliance with UDC Section 5.12.7: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-23005. Here's an overview of the RNA review process: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/planning-amp-zoning/rna-application-and-review-process.pdf. Please make sure to include in the Design Package a complete Site Plan that has addressed Zoning comments. It is not clear to this reviewer if the proposed land use is Commercial Storage, or if the proposed storage units are accessory structures to the house adjacent to the south. Please note accessory structures are not permitted by themselves on a piece of property without a principal land use. If you have any questions, please let us know: specialdistricts@tucsonaz.gov. Thank you.
12/08/2025 Fire New Construction - Standard REQUIRES RESUBMIT Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
11/26/2025 Site Engineering - Standard REQUIRES RESUBMIT Permit: TC-FBB-1125-00127
Location: 116200880
Review Date: 11/26/2025
Site Engineering Comments:
1. The parcel 116200880 appears to fall between the City of Tucson Simpon Wash Floodplain and the Simpon Wash. Due to the volume of flow and nearby base flood data, it will be required that each Conex container be required to be flood vented and affixed to the ground.
2. This will require a Floodplain use permit with elevation certificates. Please start a new FPU at our permit application web page: https://tdc-online.tucsonaz.gov/#/home
3. The FPU permit is a separate permit that can be submitted within the sub-records tab of this building permit on TDC online.
4. For the container, flood venting will be required according to Tucson Code PART II Chapter 26, Section 26-11.2.(8). For resubmission of the building permit and submission for the flood plain use permit, have the flood vents delineated on the construction plans along with a detail showing the dimensions of the vents as well as height of vents above grade.
5. A minimum of two openings will be required for each container. The vents will have a total net area of not less than one square inch for every square foot of enclosed area. Openings may be equipped with screens, louvers, valves, or other coverings or devices if they permit the automatic entry and exit of floodwater.
6. Due to the flood venting requirement, the floodplain use permit process will include elevation certificate to verify the construction and placement of the flood vents.
7. Site Engineering will be unable to approve permit TC-FBB-1125-00127 until the floodplain use permit is reviewed and approved, along with the required construction document updates.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
12/05/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-FBB-1125-00127
Parcel # 116200880
Containers on vacant lot (1st Review)

TRANSMITTAL DATE: 12/5/2025

The site is zoned C-3 (UDC 4.7.22).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The Unified Development Code 6.6.2.B states “In all zones, an accessory building shall be built only on a lot occupied by a principal building or use”. This lot is vacant so the proposed storage containers cannot be permitted in the current state of the parcel. If you wish to proceed, either provide a principal building or use on the lot or do a lot combination with the parcel you own to the South. A lot combination can be applied for through the Pima County Assessor’s Office. The lot combination request form can be found here: https://www.asr.pima.gov/Downloads/Forms/ComboRequest.pdf.
If the proposed use will be commercial, then a Development Package will be required as well. https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Development-Package.
2. Comment: As this site is located within the COT Downtown Core and Rio Nuevo Area (RNA), RNA review must be completed and approved prior to zoning approval of this building permit. Please contact Maria Gayosso at Maria.Gayosso@tucsonaz.gov if you have questions about the RNA review process. Site Zoning cannot approve this permit until the RNA review has been approved. Additional information about RNA requirements can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/planning-amp-zoning/rna-application-and-review-process.pdf.
3. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
11/25/2025 PDSD Application Completeness Express REVIEW COMPLETED