Permit Review Detail
Review Status: Requires Resubmit
Review Details: FACTORY BUILT BUILDINGS v.4
Permit Number - TC-FBB-1123-00006
Review Name: FACTORY BUILT BUILDINGS v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/22/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/22/2024 | Commercial Building | REQUIRES RESUBMIT | The below comment was not addressed. "Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Submit the approved drawings from the State of Arizona Office of Manufactured Structures along with their approval document. 2. Please coordinate with the state regarding their inspection. 3. Please resubmit." 4. You may submit an image of the Insignia attached to the chassis on each structures used, that was issued by the State to meet item 1 requirement above. 5. Show the distance of the trailers from the property line. |
||
01/18/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Provide a accurate site plan showing the location of the new temporary electrical service equipment and feeder routing to the temp trailers. 2. The Construction Staging Plan shows Generators for Tempoary Trailers. Please clarify as to what power source the Temporary Trailers will be utilizing. 3. Provide a grounding detail for the electrical service and downstream equipment that complies with NEC art 250.50, 250.52, 250.53. 4. Aluminum shall not be used as a Grounding electrode Conductor per NEC 250.64(A). Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
01/08/2024 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-FBB-1123-00006 4785 E. Valencia Rd. – PAD-21 Construction Trailers (3rd Review) TRANSMITTAL: January 8, 2024 This comment was not addressed. Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in PAD-21 (UDC 4.7.24). 1. This comment was not addressed. The proposed construction trailers require a Temporary Use Permit (TUP). The TUP is required to be approved prior to approval of this permit. Clearly show the locations of the trailers on a copy of the stamped approved Development Package, DP22-0147, and submit for a TUP. TUP requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
01/08/2024 | PDSD Application Completeness | REVIEW COMPLETED |