Review Details: FACTORY BUILT BUILDINGS v.6
Permit Number - TC-FBB-1123-00006
Review Name: FACTORY BUILT BUILDINGS v.6
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/15/2024 | Commercial Building | APPROVED | |||
03/13/2024 | Site Zoning | APPROVED | |||
03/15/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/14/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The previous plan review comment pertaining to the temporary Generators is still not addressed. The Construction Staging Plan ‘AS-103’ still shows Generators utilized for the Temporary Trailers. Show complete electrical plans showing all wiring methods, OCPD’s for the panels ‘A’ and ‘B’. 2 Ref; Plan sheet E1.0. The Riser Diagram does not show an equipment Grounds included with the 3 #4/0 feeders for the Job Trailers, also not shown for the Tap conductors from the Ingrade Pull Box to the Job Trailer panels. NEC art 250.32(B). Please clarify. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
02/29/2024 | PDSD Application Completeness | REVIEW COMPLETED |