Permit Review Detail
Review Status: Requires Resubmit
Review Details: FACTORY BUILT BUILDINGS v.3
Permit Number - TC-FBB-1023-00003
Review Name: FACTORY BUILT BUILDINGS v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/27/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/14/2023 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. On your Site Plan/Aerial, please indicate the measurements from the property lines to the trailer. 2. The following comment was not responded to. Allow me to copy and paste the previous comment: "Please submit the current State approved drawings and approval documentation for the construction trailer." |
||
12/27/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The previous electrical plan review comments are not completely addressed. 1. The power pole drawing shows 1/0 AWG THHW overhead wire between poles. The electrical line diagram and site plan shows #2 AWG AL XLP Quadraplex. Please clarify the power pole drawing and provide Registrant sealed drawing. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
12/14/2023 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-FBB-1023-00003 10100 E. Old Vail Rd. – PAD-36 Temporary Power for Construction Trailer (2nd Review) TRANSMITTAL: December 14, 2023 Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in PAD-36 (UDC 4.7.24). 1. As Temporary Use Permit TZ-PMT-1123-00116 has not yet been approved Zoning cannot approve this permit 2. This comment was not addressed. The plan for the temp power shall be provided on an approved copy of the development package sheet, 25. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
12/13/2023 | PDSD Application Completeness | REVIEW COMPLETED |