Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-FBB-0925-00114
Parcel: 14021001B

Address:
5301 S PARK AV

Review Status: Requires Resubmit

Review Details: PERMANENT MODULAR v.1

Permit Number - TC-FBB-0925-00114
Review Name: PERMANENT MODULAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2025 Commercial Building - Standard APPROVED
10/24/2025 Commercial Plumbing - Standard APPROVED
10/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/16/2025 Commercial Electrical - Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-FBB-0925-00114 (5301 S PARK AV TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
2. List the Lighting Area per OLC (Typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
4. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
5. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/29/2025 Site Engineering - Standard REQUIRES RESUBMIT TC-FBB-0925-00114
5301 S PARK AV

Site Engineering Comments are as follows:

1. This is a change to an exterior area and it's going to displace parking spots and the current dumpster location. This proposed FBB will require a Development Package that complies with the criteria found in Administrative Manual 2-06.4.0 thru 2-06.4.9.
https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-8794

2. The associated development package must be approved by all reviewers prior to the approval of this factory-built building permit. UDC Article 3.3.3.7.a
https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-841

Ryan Insalaco
Engineering Associate
ryan.insalaco@tucsonaz.gov
10/29/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-FBB-0925-00114
5301 S. Park Ave. Tucson, AZ 85706
New water vending kiosk (1st Review)

TRANSMITTAL DATE: 10/29/2025

The site is in the C-2 zone (UDC 4.7.21). Food and beverage sales is an allowed use in this zone.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
10/20/2025 Fire New Construction - Standard REVIEW COMPLETED
09/26/2025 PDSD Application Completeness Express REVIEW COMPLETED