Permit Number: TC-FBB-0924-00165
Parcel: 12912192A

Review Status: Requires Resubmit

Review Details: MANUFACTURED/MOBILE/PARK MODEL HOME v.1

Permit Number - TC-FBB-0924-00165
Review Name: MANUFACTURED/MOBILE/PARK MODEL HOME v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2024 Site Engineering NOT REQUIRED
10/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/23/2024 Residential Building REQUIRES RESUBMIT Dwelling units require six foot clear space between structures when not one hour fire rated, R302.1 (City of Tucson Amended).

Show how the existing building complies with the appropriate construction listed at IBC Table 721.1(2).
10/03/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-FBB-0924-00165
1207 E 31ST ST. – R-2
Manufactured Home Setup (1st Review)

TRANSMITTAL DATE: October 3, 2024

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). A Manufactured Home is a permitted use in this zone (Table 4.8-2), subject to Use Specific Standards 4.9.7.B.6, .9, & .10

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, to include but not limited to:
a. Provide a lot coverage calculation on the plot plan.
b. Provide a dimension from the centerline of both streets to the face of curb, where pavement meets the concrete curb and from face of curb to the property line. Based on Constructure Plan I-72-041 the distance from centerline of 31st to the face of curb is 15’ and from face of curb to the south property line is 15’, the distance from centerline of Santa Rita to the face of curb is 15’ and from face of curb to the west property line is 25.
c. Provide the square footage of the free standing carport, existing shed and gazebo shown on the plan.
d. Provide a setback dimension from the carport to the north property line.
e. Provide a setback dimension from the gazebo to the south property line.
f. Provide the wall height for the walls adjacent to the property lines for the free standing carport, existing shed and gazebo shown on the plan, see UDC Article 6.4.5.B & Figure 6.4.5-A for the correct measurement.
g. Show all utility lines on the plot plan including those to the existing residence.
h. Provide the wall heights from design grade to the highest point of the wall for the north, south and east walls of the proposed manufactured home.
i. Provide the maximum height of all structures, see UDC Article 6.4.5.A and Figure 6.4.4-A for the correct measurement.
j. Provide the zoning of the property and all adjacent properties.

2. Clearly demonstrate that the requirements of UDC Use Specific Standards 4.9.7.B.6 are met for the proposed manufactured home.

3. Zoning was not able to find approved permits or compliance review documents for the free standing carport or gazebo shown on the plan. One of the following with need to be complied with: 1) provide approved permits or compliance review documents, 2) show the structures to be removed, or 3) include these structures in this permit.

4. As the “EXISTING BUILDING” shown on the plan does not meet the minimum 20’-0” front street perimeter yard setback to the west property line, UDC Article 6.4.5.C.1.a, the required side street perimeter yard setback to the free standing carport is 10’-0”, UDC Article 6.4.5.C.1.b, and the proposed setback is 5’-0”, A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

5. As the “EXISTING BUILDING” shown on the plan does not meet the minimum 20’-0” front street perimeter yard setback to the west property line, UDC Article 6.4.5.C.1.a, 31st St. is considered the front street. Until the square footage is provided for the gazebo Zoning cannot determine if the gazebo is considered an accessory structure located in the front yard. Per UDC Article 6.6.3.C detached accessory buildings , including accessory dwelling units , are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line , except for shade structures or carports not over 400 square feet in floor area , terraces and steps not over three feet high above the natural grade , paved areas, and fences or walls. Additional comments maybe forthcoming

6. It does not appear that the carport meets the minimum perimeter yard setback of 6’-0” or 2/3 the height of the exterior wall, greater of the two.

7. Additional comments may be forthcoming.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/23/2024 PDSD Application Completeness Express REVIEW COMPLETED The permit and plan shows to be for a secondary dwelling on this property and this requires to have its own address. A pre issuance addressing condition has been placed on permit. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to assign/add the units or a new address for this manufactured home. Please submit an address change request once the addressing issue has been resolved. For questions: Building_Official@tucsonaz.gov