Permit Number: TC-FBB-0625-00090
Parcel: 105110490

Address:
4646 N ORACLE RD

Review Status: Requires Resubmit

Review Details: FACTORY BUILT BUILDINGS v.1

Permit Number - TC-FBB-0625-00090
Review Name: FACTORY BUILT BUILDINGS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2025 Commercial Building APPROVED
07/16/2025 Site Zoning APPROVED
07/16/2025 Site Engineering NOT REQUIRED
07/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/02/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-FBB-0625-00090 (4646 N ORACLE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide the service size and rating of the equipment.
2. Provide an electrical riser diagram, 2017 NEC 230.9. Notate the grounding and bonding method, 2017 NEC 250.20(B), 250.24, 250.30(A)(4). (The TEP SR-307 sheets are for a pole mounted service entrance, while the plans appear to show the service entrance located on the building.)

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/01/2025 PDSD Application Completeness Express REVIEW COMPLETED