Permit Review Detail
Review Status: In Review
Review Details: FACTORY BUILT BUILDINGS v.3
Permit Number - TC-FBB-0426-00050
Review Name: FACTORY BUILT BUILDINGS v.3
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Commercial Mechanical | PENDING ASSIGNMENT | |||
| 05/19/2026 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-FBB-0426-00050 (3300 S PARK AV TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. S/O cord is not an approved wiring method in the NEC chapter 3, nor is this a listed permitted use in NEC 400.10. 2. Provide connection from the generator to the trailer using an approved wiring method for this use. |
||
| 05/12/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |