Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/24/2026 Commercial Building - Standard REQUIRES RESUBMIT
04/21/2026 Commercial Electrical - Standard REQUIRES RESUBMIT Commercial Electrical Review TC-FBB-0426-00049 (5211 E VALENCIA RD TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The submitted plans are for permit TC-COM-1225-02209 and are not related to the stated scope of work for adding a ‘office/connex-40' and a 40' storage container’. Please submit ONLY appropriate plans for the stated scope of work.
2. Provide an updated site plan showing the location of the office/conex and storage containers.
3. Provide electrical plans showing how power is getting to the units.

Additional comments may be forthcoming with correct and complete building plans.
04/24/2026 Commercial Mechanical - Standard REQUIRES RESUBMIT ACTIVITY NO. TC-FBB-0426-00049
ADDRESS/PARCEL: 5211 E VALENCIA RD TUCSON, AZ 85706

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The documents submitted do not match the scope of work for this permit. The application is for a office/connex-40' and a 40' storage container (FBB structures), however, the plans provided are for the Panda Express restaurant previously reviewed (TC-COM-1225-02209). No information or details related to the proposed shipping/storage containers are included in the submittal. Please provide plans that accurately reflect the proposed scope of work, including the location and details of the office/connex-40' and the 40' storage container. Reference: Section 107.2.1, IBC 2024.
04/24/2026 Commercial Plumbing - Standard REQUIRES RESUBMIT ACTIVITY NO. TC-FBB-0426-00049
ADDRESS/PARCEL: 5211 E VALENCIA RD TUCSON, AZ 85706

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The documents submitted do not match the scope of work for this permit. The application is for a office/connex-40' and a 40' storage container (FBB structures), however, the plans provided are for the Panda Express restaurant previously reviewed (TC-COM-1225-02209). No information or details related to the proposed shipping/storage containers are included in the submittal. Please provide plans that accurately reflect the proposed scope of work, including the location and details of the office/connex-40' and the 40' storage container. Reference: Section 107.2.1, IBC 2024.
04/27/2026 Fire New Construction - Standard REQUIRES RESUBMIT -Provide appropriate submittal. See others comments.
john.vincent@tucsonaz.gov
5203495581
04/27/2026 Site Engineering - Standard REQUIRES RESUBMIT Site Engineering Review

TC-FBB-0426-00049
5211 E VALENCIA RD

Description: office/connex-40' and a 40' storage container

Site Engineering comments are as follows:

1. The plans provided with this proposal do not match the scope of work described in the summary of the permit.
2. Provide plans which show the actual location of the proposed container and office. Show any proposed utilities, even if they are proposed to be temporary. Show easements and setbacks from the property lines. See the Full Site Plan Example for more information.

https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/plan-samples/full-site-plan_feb2026.pdf

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
04/15/2026 PDSD Application Completeness Express REVIEW COMPLETED