Permit Number: TC-FBB-0326-00033
Parcel: 135074480

Review Status: Requires Resubmit

Review Details: SHIPPING CONTAINER v.1

Permit Number - TC-FBB-0326-00033
Review Name: SHIPPING CONTAINER v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/13/2026 Commercial Building - Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please indicate the use of the Container and type of the container, provide a foundation and anchoring system design, with calculations and construction drawings prepared and sealed by an Arizona Registrant that adequately show the scope of work and compliance with the adopted building codes. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. If the use is Storage, provide a code analysis and indicate exactly what is to be stored in the container.
3. Please provide a dimensioned site plan following the guidance in the below link. Additionally, if the use is other than storage, or if any utilities are installed, please prepare plans in accordance with the City of Tucson Commercial Submittal Requirements. See link
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/14/2026 Fire New Construction - Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
03/31/2026 Site Engineering - Standard REQUIRES RESUBMIT Permit: TC-FBB-0326-00033 – Shipping Containers
Location: 1401 S PANTANO RD
Review Date: 3/31/2026

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-06 and Technical Manual (TM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code.

Drainage Manual Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage…

Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-rete…

Overall, for application submittal requirements, see Administrative Manual Section 2-06

Site Engineering:

1. After reviewing the plan set, it does not match up with the approved site plans from associated development package TD-DEV-0126-00018. The location of the three shipping containers does not quite match as approved in which they are shown on the southeast of the parking lot away from the existing building. It will be required that either the DP be revised to demonstrate what is being proposed or revise the FBB plans to align with approved site plans.

If you have any questions or concerns, please contact Joe Macaulay at: Joe.Macaulay@tucsonaz.gov
04/08/2026 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-FBB-0326-00033 - TD-DEV-0126-00018
1401 S. Pantano Rd. Tucson, AZ 85710
Storage Container (1st Review)

TRANSMITTAL DATE: 4/8/2026

The site is zoned I-1 (UDC 4.7.29).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The associated Development Package (DP) TD-DEV-0126-00018 shows the storage unit being placed in a different location. Please ensure the placement matches where it was proposed in the DP. If the placement of the unit has changed, please revise your DP to show the new location.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
03/16/2026 PDSD Application Completeness Express REVIEW COMPLETED