Permit Number: TC-FBB-0326-00032
Parcel: 135074480

Review Status: Requires Resubmit

Review Details: SHIPPING CONTAINER v.1

Permit Number - TC-FBB-0326-00032
Review Name: SHIPPING CONTAINER v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/14/2026 Commercial Building - Standard REQUIRES RESUBMIT ACTIVITY NO. TC-FBB-0326-00032
ADDRESS/PARCEL: (1401 S PANTANO RD TUCSON, AZ 85710)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. US Chemical Storage
a. The above company is the manufacturer of this FL1907 chemical storage unit.
b. Per the manufacturer, this storage unit is a code-compliant chemical storage ready to ship and install.
c. The City of Tucson concludes that the State of Arizona categorizes this as an FBB (Factory Built Structure).
d. Please contact the State of Arizona Department of Housing and inquire about their Factory Built Building Installation Permit as well as their Installation Plan Review Approval.
e. Please contact the State of Arizona Factory Built Buildings using the contact info within this following website Contact Us | Department of Housing.
f. Submit the State approved/sealed/dated documents/drawings by uploading it with your response to these comments into your building permit record via the city’s online website. (Note, should the state declines to process…. Please submit the state’s refusal letter containing their letter head allowing the city to process.
2. DURATION
a. Is this installation going to be permanent.
b. If so, Foundation/Footing and Anchoring System shall be required.
c. Please submit detail drawings of the required footing and achoring system used.
3. LOCATION
a. The drive aisle as directly adjacent to this FBB as shown on the aerial site plan. The traffic on the drive aisle is not allowed to be impdeded.
b. Please enter the dimension between the FBB and the drive aisle.
c. Please enter the dimension between equipment enclosure fence enclosure and the FBB. The gates and accessibility must be allowed to function properly.
4. ELECTRICAL
a. According to the manufacturer’s website, this FL1907 chemical storage unit required electrical power.
b. The website also mentions this unit as having air conditioning unit and exhaust fans.
c. Please submit electrical drawings.
5. RAMP
a. Ramp is an option for this FL1907 chemical storage unit.
b. Should this be selected as an option, please do show this on your drawing making sure proper dedicated area for it to function property with its required clearances and code compliant per ICC A117.1.
6. NOTE******Submit the list of hazardous materials along with their quantities and maximum allowable quantity per control area according to IBC 414. Please do this for every chemical storage unit on the site.
7. Please resubmit.
05/05/2026 Commercial Electrical - Standard REQUIRES RESUBMIT Commercial Electrical Review TC-FBB-0326-00032 (1401 S PANTANO RD TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide a site electrical plan showing how power is getting to the manufactured home. Show exiting and new electrical equipment, transformer, panel etc. Show Underground electoral lines and conductor sizes/types. Show conduit types and size.
2. Provide an electrical riser diagram, NEC 230.9. Notate the grounding and bonding method, NEC 250.20(B), 250.24, 250.30(A)(4). Metallic gas lines must be bonded and not be used as the primary grounding method, NEC 250.50, 250.52(B)(1).
a. Show each meter and address/unit associated with each meter.
b. Show bus bar rating and AIC ratings.
05/11/2026 Commercial Mechanical - Standard REQUIRES RESUBMIT ACTIVITY NO. TC-FBB-0326-00032
ADDRESS/PARCEL: 1401 S PANTANO RD TUCSON, AZ 85710
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The State of Arizona categorizes these structures as Factory Built Buildings (FBB). Please contact the Arizona Department of Housing regarding the required Factory Built Building installation permit and installation plan review approval. Please submit the approved/sealed/dated documents and drawings from the State by uploading them through the City’s online permitting portal.
04/14/2026 Fire New Construction - Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
03/31/2026 Site Engineering - Standard REQUIRES RESUBMIT Permit: TC-FBB-0326-00032 – Shipping Containers
Location: 1401 S PANTANO RD
Review Date: 3/31/2026

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-06 and Technical Manual (TM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code.

Drainage Manual Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage…

Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-rete…

Overall, for application submittal requirements, see Administrative Manual Section 2-06

Site Engineering:

1. After reviewing the plan set, it does not match up with the approved site plans from associated development package TD-DEV-0126-00018. The location of the three shipping containers does not quite match as approved in which they are shown on the southeast of the parking lot away from the existing building. It will be required that either the DP be revised to demonstrate what is being proposed or revise the FBB plans to align with approved site plans.

If you have any questions or concerns, please contact Joe Macaulay at: Joe.Macaulay@tucsonaz.gov
04/08/2026 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-FBB-0326-00032 - TD-DEV-0126-00018
1401 S. Pantano Rd. Tucson, AZ 85710
Storage Container (1st Review)

TRANSMITTAL DATE: 4/8/2026

The site is zoned I-1 (UDC 4.7.29).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The associated Development Package (DP) TD-DEV-0126-00018 shows the storage unit being placed in a different location. Please ensure the placement matches where it was proposed in the DP. If the placement of the unit has changed, please revise your DP to show the new location.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
03/16/2026 PDSD Application Completeness Express REVIEW COMPLETED