Permit Number: TC-FBB-0325-00045
Parcel: 118060600

Review Status: Requires Resubmit

Review Details: FACTORY BUILT BUILDINGS v.2

Permit Number - TC-FBB-0325-00045
Review Name: FACTORY BUILT BUILDINGS v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2025 Site Engineering NOT REQUIRED
05/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/24/2025 Residential Building REQUIRES RESUBMIT Clarify which building are proposed with this permit. The Site Plan shows both a proposed residence and a RV for living space in addition to an office and garage.

Submit a set of construction plans showing 2018 IRC building compliance after zoning approval of proposed usage.

Show the location and size of buildings, utility meters and gas, water & electric lines from property line to building, R106.1.1. Include the square footage of each structure type.
04/30/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-FBB-0325-00045
1007 W PRINCE RD Unit: 41 – R-1
Class A RV to use as living quarters and a travel trailer to be used as office (1st Review)

TRANSMITTAL DATE: April 30, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

\This site is located in the R-1 zone (UDC 4.7.8). An RV used for a residence is not a permitted use in this zone (Table 4.8-2).

1. Per UDC Table 4.8-2 an RV cannot be used as a residence in the R-1 Zone. A possible solution would be to obtain a Temporary Use Permit (TUP) to allow the RV to be used for a specified amount of time. TUP requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications. Contact for the TUP is Mark Castro, 520.837.4979 or Mark.Castro@tucsonaz.gov.

2. An office use in the R-1 Zone may only be done as a Home Occupation. The Home Occupation must meet all requirements of UDC Article 4.9.7.E. Clearly demonstrate that these requirements are met for the proposed office. The travel trailer may not be used as an office. Travel trailers may only be stored on an R-1 zoned property not occupied.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/24/2025 PDSD Application Completeness Express REVIEW COMPLETED