Permit Number: TC-FBB-0226-00015
Parcel: 10603039C

Review Status: Requires Resubmit

Review Details: SHIPPING CONTAINER v.1

Permit Number - TC-FBB-0226-00015
Review Name: SHIPPING CONTAINER v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/20/2026 Commercial Building - Standard REQUIRES RESUBMIT ACTIVITY NO. TC-FBB-0226-00015
ADDRESS/PARCEL: (3344 N STONE AV Unit:BLDG 3 TUCSON, AZ 85705)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. ELECTRICAL
a. Is light going to be required in this container?
b. If so, please submit electrical drawing.
2. ANCHOR
a. Foundation/Footing is required.
b. Anchoring is required per International Building Code 2024 section 1604.8.1.
c. Please submit detail drawings of the required footing and achoring system used.
3. LOCATION
a. Please enter the dimension between the existing building exterior wall and the container.
b. Please enter the dimension between dumpster enclosure wall and the container.
4. Please resubmit.
03/20/2026 Fire New Construction - Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov / 520.837.7082
03/03/2026 Site Engineering - Standard REQUIRES RESUBMIT Permit: TC-FBB-0226-00015 – Container In floodplain
Location: 3344 N STONE AV Unit: BLDG 3
Review Date: 3/3/2025
Site Engineering Comments:
1. The proposed shipping container to the existing commercial/Multifamily site will require the submission of a Development Package Site plan UDC 7.4.3.E as this constitutes as site work. In accordance with Unified Development Code (UDC) Article 3.3.3.G.2.c, a site plan (Development Package Permit) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.
a. Note, as the container is proposed with the Navajo FEMA AE Floodplain, the development package (Site Plan) submission will require the submission of a drainage statement sealed by a registered Civil Engineer. The drainage document must demonstrate no adverse impacts caused by the placement of the container. The encroachment analysis will need to show that the container do not create an adverse impact to surrounding properties or affect drainage up or down stream, including assessment of velocities, depths, erosive capacity, direction of flow, and increased scour conditions, etc. Keep in mind adjacent properties are Pre-FIRM and may not have elevated pads.
b. If it appears the project creates adverse impacts, then it will not be allowed as proposed.
2. Site Engineering is unable to review and approve permit TC-FBB-0226-00014 until the associated Development Package is reviewed and approved by all reviewers.
3. For resubmission of the FBB permit, provide the approved site plan to show clearly where the container will be located
4. This project lies within a FEMA AE Floodplain associated with the Navajo Wash and will require the submission of a floodplain use permit with elevation certificate. The FPU permit is a separate permit that can be submitted within the sub-records tab of this building permit on TDC online.
a. Due to the floodplain, it will be required that the Conex container be flood vented and affixed to the ground. Due to the flood venting requirement, the floodplain use permit process will include elevation certificate to verify the construction and placement of the flood vents.
b. For the container, flood venting will be required according to Tucson Code PART II Chapter 26, Section 26-11.2.(8). For resubmission of the building permit and submission for the flood plain use permit, have the flood vents delineated on the construction plans along with a detail showing the dimensions of the vents as well as height of vents above grade.
c. A minimum of two openings will be required for the container. The vents will have a total net area of not less than one square inch for every square foot of enclosed area. Openings may be equipped with screens, louvers, valves, or other coverings or devices if they permit the automatic entry and exit of floodwater.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
03/19/2026 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-FBB-0226-00015
3344 N. Stone Ave Bldg. 3 Tucson, AZ 85705
New 20’ x 8’ x 8.5’ Shipping Container (1st Review)

TRANSMITTAL DATE: 3/19/2026

This site is located in the R-3 zone (UDC 4.7.12). Multifamily is a permitted use in this zone (UDC Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the minimum requirements is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/submittal_requirements.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
02/20/2026 PDSD Application Completeness Express REVIEW COMPLETED