Permit Review Detail
Review Status: Requires Resubmit
Review Details: FACTORY BUILT BUILDINGS v.1
Permit Number - TC-FBB-0225-00016
Review Name: FACTORY BUILT BUILDINGS v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/17/2025 | Site Engineering | NOT REQUIRED | |||
| 03/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/12/2025 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please indicate on the plans the Job Office is not to be used by the public and will be installed in accordance with the manufacturer's instructions, or apply with the State of Arizona office of Housing (ADOH) for FBB approval of FBB and installation permit . IBC 107.2.1 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 03/05/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-FBB-0225-00016 (7150 E SPEEDWAY BL TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). 1. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1. 2. Provide an updated panel schedule, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4. 3. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. 4. Show the location of the panel on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A) 5. Provide an electrical riser diagram, 2017 NEC 230.9. Notate the grounding and bonding method, 2017 NEC 250.20(B), 250.24, 250.30(A)(4). Metallic gas lines must be bonded and not be used as the primary grounding method, 2017 NEC 250.50, 250.52(B)(1). Outdoor Lighting Review: 1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan 2. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 3. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. 4. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. 5. Specify any exceptions used. 6. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/10/2025 | Site Zoning | REQUIRES RESUBMIT | The plan used for the construction trailer shall be a copy of stamped approved sheet 6 of development package TD-DEV-0524-00143. A Temporary Use Permit (TUP) will be required. TUP requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications. Contact for the TUP is Mark Castro, 520.837.4979 or Mark.Castro@tucsonaz.gov. | ||
| 03/05/2025 | Fire New Construction | REVIEW COMPLETED | Project shall comply with the 2024 IFC Section 505 Premise identification, add fire access signs at entrance gates. On site fuel dispensing or storage will required a separate permit, contact Jesus.silva@tucsonaz.gov for additional instructions. site shall comply with chapter 33 IFC 2024," Fire Safety During Construction" |
||
| 02/25/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |