Review Details: PERMANENT MODULAR v.1

Permit Number - TC-FBB-0124-00008
Review Name: PERMANENT MODULAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2024 Fire New Construction NOT REQUIRED
02/27/2024 Site Engineering NOT REQUIRED
03/06/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/06/2024 Residential Building REQUIRES RESUBMIT 1. For clarity please label the panels and provide a panel schedule for the Existing Panel showing the disconnecting means ( Circuit Breaker) for the down stream panel shown as Panel B in the State approved drawings.

Mark Masek
Plans Examiner
Mark.masek@tucsonaz.gov
520-837-4994
02/22/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-FBB-0124-00008
1501 E PROSPECT LN Unit: 2. – MH-1
FBB 1bd 1bth connected to kitchen model (1st Review)

TRANSMITTAL DATE: February 22, 2024

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Clarify what is proposed. The description provided on the application states “FBB 1bd 1bth connected to kitchen model” and under “PROJECT DESCRIPTION” on the plan it states “Residential ADU”.

The following comments are based on this plan being permitted as an accessory dwelling unit (ADU). MH-1 zone (UDC 4.7.10). A single-family residence with and ADU is a permitted use in this zone (Table 4.8-2), subject to Use Specific Standards 4.9.7.B.6, 8, & 9 and 6.6.3.

1. Per UDC Article 6.6.3.C Detached accessory buildings, including accessory dwelling units, are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line. A Board of Adjustment for Variance must be submitted and approved to allow the ADU as shown on the plan. Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. Contact for the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov.

2. Clearly demonstrate that the requirements of UDC Article 6.6.3.B.2, .3, .4 & .5 are met.

The following comments are based on this plan being permitted as 2nd dwelling unit (SFR). MH-1 zone (UDC 4.7.10). Two (2) single-family residences are a permitted use in this zone (Table 4.8-2).

1. Per UDC Article 6.4.5.C.1.a the minimum front street perimeter yard is 20’-0”, proposed front street is 10’-0”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
01/30/2024 PDSD Application Completeness Express REVIEW COMPLETED