Permit Number: TC-DMO-0424-00064
Parcel: 140420790

Review Status: Requires Resubmit

Review Details: DEMOLITION v.1

Permit Number - TC-DMO-0424-00064
Review Name: DEMOLITION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2024 Site Zoning APPROVED
04/11/2024 Site Engineering NOT REQUIRED
04/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/16/2024 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-DMO-0424-00064
ADDRESS/PARCEL: (2705 E MEDINA RD Unit:UNIT 111 TUCSON, AZ 85756)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. This is not a demolition permit.
2. This is a Tenant Improvement with Partial demolition, New Flooring, New Ceiling, Mechanical and Electrical work (Fire Sprinkler/Alarm deferred submittal).
3. Please apply for the correct permit as described in item #2 above.
4. Show all Electrical and Mechanical in all Offices, Breakroom and Corridors. If they are existing, label them as existing to remain.
5. Please resubmit.
04/15/2024 Commercial Electrical REQUIRES RESUBMIT Please see Mechanical Plan review comments and resubmit accordingly.
Ref' 2018 IBC section 107.2.1.
04/15/2024 Commercial Mechanical REQUIRES RESUBMIT Demolition permits are for demolition only, not for the subsequent additions or alterations.
04/09/2024 Fire New Construction REVIEW COMPLETED
04/05/2024 PDSD Application Completeness Express REVIEW COMPLETED Interior demo only, A separate Commercial Addition/Alteration permit is required for any and all other tenant improvements.