Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1225-02344
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/28/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov 1. Please amend the plans to add existing internal property lines to the site plans. IBC 107.2.6 2. Please amend the plans to provide a dimensioned front and side elevation of the Roof Ladder. 11/A1.04 in named a Ships Ladder; however, please provide a drawing of a roof access ladder as described in IMC 306.5 3. Please amend the plans to include list of deferred submittals with a note to not install until approved. IBC 107.3.4.1 4. Please amend the plans to show required handrail(s)/edge protection on the east elevation if the rise exceeds 6 inches. IBC 1012.8 & IBC 1012.10 5. Please provide the structural calculations and the geotechnical report used in the design of this building with your next submittal. IBC 107.2.7 6. Please provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link: Special Inspection Certificate Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 01/14/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1225-02344 (4333 E SPEEDWAY BL TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide a general electoral notes sheet which includes an electrical symbol and abbreviation legend. 2. Provide Ground Fault Protection for personnel per NEC 210.8(B)(8) & NEC 511.12. 3. Provide or show compliance with NEC article 511 for Commercial Garages, Repair and Storage buildings, including any Hazardous Classification zones and wiring methods, NEC 511. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/27/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Verify that the distance between the high volume propellor fans and the HVAC diffusers complies with the manufacturer’s clearance requirements. Reference: Section 304.1, IMC 2018. 2. Condensate drains shall be terminated at an approved disposal location (i.e. a splash block on the roof is not an approved location). Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. 3. If the motor vehicles will be operated for more than the time required to move in and out of the building, provide a design for a source-capture exhaust system for operating motor vehicles. Reference: Section 502.14, IMC 2018. 4. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. |
||
| 01/26/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. Provide secondary (overflow) roof drainage. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018. 2. Provide the location, travel path, and total travel distance from the new building to existing toilet facilities. Verify that the existing toilet facilities will accommodate the additional population. Reference: Sections 2902.1 and 2902.3.3, IBC2018. |
||
| 01/14/2026 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-1225-02344 (4333 E SPEEDWAY BL TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code. 2. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan. 3. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. 5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. 6. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 7. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type. 8. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf 9. Specify any exceptions used. 10. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/05/2026 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-1225-02344 Location: 4333 E SPEEDWAY BL Review Date: 1/5/2025 Site Engineering Comments: 1. Site Engineering has reviewed the building plans for compliance with development package TD-DEV-1225-00306. Until the development package is approved by all reviewers, site engineering will be unable to approve permit TC-COM-1225-02344. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 01/22/2026 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: Ramiro Olivarez PDSD Zoning Review Section PROJECT: TC-COM-1225-02344 - TD-DEV-1225-00306 4333 E SPEEDWAY BL New Masonry Building -12 bay automotive service – C-2 (1st Review) TRANSMITTAL DATE: January 22, 2026 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Comment: Zoning has reviewed the building plans for compliance with development package (DP TD-DEV-1225-00306. Site Zoning cannot approve this building permit until all review agencies have approved DP TD-DEV-1225-00306. 2. Comment: On cover sheet G0.00, under the Code Summary, the information listed for Allowable Building Height and Area is incorrect and does not match the related dimensional standards in the associated DP (TD-DEV-1225-00306). Correct to match. 3. Comment: Additional comments may be forthcoming on the next review based on the proposed use. If you have any questions about this transmittal, please contact Ramiro.Olivarez@tucsonaz.gov |
||
| 01/26/2026 | Water - PDSD Standard | REQUIRES RESUBMIT | Verify the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. | ||
| 01/26/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 01/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |