Permit Number: TC-COM-1225-02341
Parcel: 116205510

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-1225-02341
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2026 Commercial Plumbing Standard APPROVED
06/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/30/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Jeffrey W. Cassidy, Planner
Planning & Development Services Department – Current Zoning Review Section

PROJECT: TC-COM-1225-02341 – Commercial – TI IN EXISTING 2 STORY 2,925 SF BLDG
185 S AVENIDA DEL SEMBRADOR TUCSON, AZ 85745 (PAD-10 Zoning)
Commercial Building Review – 3rd Review

TRANSMITTAL DATE: June 30, 2026

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

1. COMMENT: Zoning acknowledges receipt of a development package submittal, TD-DEV-0226-00037. Until this submittal has been reviewed and approved, TC-COM-1225-02341cannot be approved. Resubmit TC-COM-1225-02341-0526-00652 after TD-DEV-0226-00037 has been approved and be sure to include any modifications that may take place in that development package.

2. COMMENT: Update the TS1 sheet to include the approved Retail Wine Sales and Tasting Room use.

3. COMMENT: Update the TS1 sheet to include the approved case number TP-MOD-0226-000023 and TD-DEV-0226-00037 in the lower right hand of the sheet (above Area Calculations).

4. COMMENT: Per the May 11, 2026 Director approval letter, update the TS1 sheet to remove ‘Minor Amendment is in process’ under the Project Narrative.

5. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
1. Corrected commercial building permit
2. Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home .

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .
06/10/2026 Water - PDSD Standard REQUIRES RESUBMIT Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (see also Tucson Water Standard Detail 1802). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code. [Second comment: Comment not addressed.] [Initial comment: Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf]

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/09/2026 PDSD Application Completeness Express REVIEW COMPLETED