Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-1225-02341
Parcel: 116205510

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02341
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2026 Commercial Electrical Standard APPROVED
01/27/2026 Design Review Standard NOT REQUIRED Property in Menlo Park Mercado Dist. PAD.
01/13/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
01/05/2026 Site Engineering Standard NOT REQUIRED
01/29/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/27/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend the Code analysis to state this is a to indicate the mixed-occupancy use, and provide a 2-hr fire separation between the Wine Tasting and the residential use IBC 508.1 and IBC Table 508.4
2. Alternatively, provide fire sprinklers and permit this project as a Live Work unit per IBC 419 and the separation is not required if designed per 419.
3. Please indicate why the upper level has a R-2 occupancy and not a R-3
4. Please amend the plans to reflect the occupancy group to be a B occupancy (A-2 with an Occupant load of less than 50) IBC 303.1 & IBC 303.1
5. Please provide the following information on the plans.
A. The number of occupants is shown for every room and space. IBC 107.2.3
B. The occupant load factor and area are shown for every room and space. IBC 1004.5
C. The occupant load factor used reflects the use/function of the space. IBC 1004.5
For example, provide a furniture plan showing the Shopping space, Wine Tasting and Shop Seating spaces and the Occupant load factor used. If tables and chairs are used IBC Table 1004.5 uses 15SF per person. The occupant load is likely 30-40 depending on the uses. The shopping area could use 60 SF per occupant, the wine tasting would likely be 7 SF per occupant if chairs are provided, and the shop seating would use 15 SF per person if tables and chairs were provided.
6. Please provide a 2-hour fire separation between the residential and commercial uses. IBC Table 508.4 to include floor and ceiling for mixed-occupancy. For new 2-hour fire-rated assemblies, provide construction details with basis of approval by one of the following:
A. Listing number approved by third-party testing agency (i.e., UL, GA)
B. Item number for prescriptive fire-resistive assembly under IBC Table 721.1(2)
C. Prescriptive assembly constructed under IBC 722.6.
7. Please show the following accessibility information.
Where an entire building undergoes a change of occupancy, it shall comply with Section 305.4.1 and shall have all of the following accessible features:
1.Not fewer than one accessible building entrance.
2.Not fewer than one accessible route from an accessible building entrance to primary function areas.
3.Signage complying with Section 1111 of the International Building Code.
4.Accessible parking, where parking is being provided.
5.Not fewer than one accessible passenger loading zone, where loading zones are provided.
6.Not fewer than one accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
01/26/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. The 2018 IMC and the 2018 IECC (Residential) with Local Amendments are the relevant codes for this project, not the 2018 IRC as shown on M2.1.
2. Provide the minimum required specifications for the proposed second floor kitchen hood. Reference: Section 403.3.2.3, IMC 2018.
01/26/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
2. Show how condensate and ice melt will be drained from the proposed ice maker , P8. Reference: Section 303.2, IPC 2018.
3. For what uses will the 3-compartment sink be used? If the 3-compartment sink is used only for washing, rinsing, and sanitizing utensils used for food service, the sink shall drain indirectly to the grease interceptor with an air gap or an air break. If, however, the 3-compartment sink is also used for the preparation of food items, separate indirect waste pipes shall be provided for each compartment to protect against cross-contamination or fouling and each indirect drain shall terminate with an air gap. Reference: Sections 801.2, 802.1.1, and 802.1.7, IPC 2018.
4. Revise the natural gas schematic to show the loads and developed lengths of the natural gas piping to the new air conditioning appliances, FC-1 and RTU-1. Reference: Section 107.2.1, IBC 2018 and Sections 402.1 and 402.3, IFGC 2018.
01/29/2026 Entitlements Standard REQUIRES RESUBMIT This project requires a modification to the Mercado District PAD, as discussed in pre-application here:
https://pro.tucsonaz.gov/plandetails/TP-PRE-1025-00215/

This modification must be approved, and a signed decision notice uploaded with your building permit application prior to approval.
01/22/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
PDSD Zoning Review Section

PROJECT:
TC-COM-1225-02341
185 S. Avenida Del Sembrador Tucson, AZ 85745
TI Turning First Floor into Retail/Wine Tasting Area (1st Review)

TRANSMITTAL DATE: 1/22/2026

Comment: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

This site is located in the PAD-10 zone (Menlo Park Mercado District PAD).

1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.
2. Comment: TP-PRE-1025-00215 zoning comments state “Retail – Alcoholic Beverage Sales” is not a permitted use in this PAD. An amendment to PAD-10 will be required to permit alcoholic beverages sales at this location (Page 12, PAD-10 https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/mercado_district_pad.pdf).
3. Comment: As this site is located within the Rio Nuevo Area (RNA), RNA review must be completed and approved prior to zoning approval. Please contact Maria Gayosso at Maria.Gayosso@tucsonaz.gov if you have questions about the RNA review process. Additional information about RNA requirements can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/planning-amp-zoning/rna-application-and-review-process.pdf.
4. Comment: Site zoning is unable to approve this permit until a Development Package has been approved, RNA review has been approved, and the PAD-10 document has been amended to allow for the proposed new use.
5. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
01/26/2026 Water - PDSD Standard REQUIRES RESUBMIT Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf
01/22/2026 Fire New Construction Standard REVIEW COMPLETED
12/31/2025 PDSD Application Completeness Express REVIEW COMPLETED