Permit Number: TC-COM-1225-02338
Parcel: 10925042A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1225-02338
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/12/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing fixtures P2, P4, and a hub drain are shown using a common vent. A common vent is limited to serving two traps or trapped fixtures. Reference: Section 911.1, IPC 2018. [Second comment: The listing information for the Waterflow Refill Station calls for a forced drain using a saddle-type connection to the sanitary drain system. Saddle-type fittings are prohibited by the 2024 IPC. Show how the unit will be connected to the sanitary drain system (e.g. indirect waste with an air gap).] [Initial comment: Provide listing information for the Waterflow Refill Station. Reference: Section 107.2.1, IBC 2018.]
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
05/05/2026 PDSD Application Completeness Express REVIEW COMPLETED