Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-1225-02338
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/12/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing fixtures P2, P4, and a hub drain are shown using a common vent. A common vent is limited to serving two traps or trapped fixtures. Reference: Section 911.1, IPC 2018. [Second comment: The listing information for the Waterflow Refill Station calls for a forced drain using a saddle-type connection to the sanitary drain system. Saddle-type fittings are prohibited by the 2024 IPC. Show how the unit will be connected to the sanitary drain system (e.g. indirect waste with an air gap).] [Initial comment: Provide listing information for the Waterflow Refill Station. Reference: Section 107.2.1, IBC 2018.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 05/05/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |