Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-1225-02337
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/01/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | The calculation of the heating/cooling loads required by Section C403.2.1, IECC 2018 is to be based on the present, not the future loads. Recalculate the heating/cooling loads, including the ventilation requirements for the current restaurant. Reference: Section C403.2.2, IECC 2018. [Initial comment: The submitted heating and cooling load calculations indicate a total sensible cooling coil load of approximately 89.3 MBH, while the proposed design includes three 5-ton HVAC units with a combined sensible cooling capacity significantly exceeding the calculated load. Please provide additional justification demonstrating that the proposed equipment sizing complies with the intent of the load calculations or revise the equipment selection accordingly. Reference: Sections C403.1.1 and C502.2.3, IECC, 2018.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 07/10/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 06/25/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |