Permit Number: TC-COM-1225-02337
Parcel: 123020840

Address:
2526 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1225-02337
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/01/2026 Commercial Mechanical Standard REQUIRES RESUBMIT The calculation of the heating/cooling loads required by Section C403.2.1, IECC 2018 is to be based on the present, not the future loads. Recalculate the heating/cooling loads, including the ventilation requirements for the current restaurant. Reference: Section C403.2.2, IECC 2018. [Initial comment: The submitted heating and cooling load calculations indicate a total sensible cooling coil load of approximately 89.3 MBH, while the proposed design includes three 5-ton HVAC units with a combined sensible cooling capacity significantly exceeding the calculated load. Please provide additional justification demonstrating that the proposed equipment sizing complies with the intent of the load calculations or revise the equipment selection accordingly. Reference: Sections C403.1.1 and C502.2.3, IECC, 2018.]
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
07/10/2026 Fire New Construction Standard REVIEW COMPLETED
06/25/2026 PDSD Application Completeness Express REVIEW COMPLETED