Permit Number: TC-COM-1225-02337
Parcel: 123020840

Address:
2526 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02337
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2026 Commercial Electrical Standard APPROVED
01/23/2026 Commercial Plumbing Standard APPROVED
01/12/2026 Outdoor Lighting Standard APPROVED
01/23/2026 Water - PDSD Standard APPROVED
01/26/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/26/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend the plans to include a more complete, detailed description of the work involved in this permit’s scope. IBC 105.3 For example, it appears some interior remodeling is taking place.
2. Please amend plans to identify the specific water resistive barrier to be used. IBC 1403.2
3. Please provide the EIFS system to be used as well as an evaluation report number and provide the report. IBC 1407.2
4. Please provide an architectural special inspections certificate for: EIFS and the Water-resistive barrier as required. IBC 1705.17- 1705.17.1 For example, if the water resistive barrier is an applied coating, a special inspection is required.
A. Exceptions: Special inspections shall not be required for EIFS applications installed over a water-resistive barrier with a means of draining moisture to the exterior.
5. Please provide a wall type legend and a full wall assembly section drawing calling out the interior wall covering, sheathing wall stud type, fire blocking, and spacing, insulation type and R-value sheathing, water-resistive water barrier type, and exterior wall covering with referenced callouts and a reference where to find the information on the plan set. IBC 107.2.1 Please treat as a typical note for each unique wall type. And list wall types on the floor plan.
6. Please provide a COMcheck report with the next submittal. IECC C401.2. Additionally show the following on the plans; R-value for batt and continuous insulation with location. IECC C402.1,
7. Please add a note to the plans by the deferred submittals with a note to not install until approved. IBC 107.3.4.1
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
01/23/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02337
ADDRESS/PARCEL: 2526 E GRANT RD TUCSON, AZ 85716

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
01/23/2026 Fire New Construction Standard REQUIRES RESUBMIT -Please explain the which compliance method you are using IEBC 301.3. The compliance method, level of alteration and work area will be used to determine the fire protection system requirements (fire sprinklers) per IEBC.
john.vincent@tucsonaz.gov
5203495581
01/22/2026 Site Engineering Standard REQUIRES RESUBMIT Refer to Site Zoning comments
01/22/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-1225-02337
2526 E. Grant Rd. Tucson, AZ 85716
Tenant Exterior Renovation (1st Review)

TRANSMITTAL DATE: 1/22/2026

This site is located in the C-2 zone (UDC 4.7.21). Food Service: Excluding Soup Kitchens is an allowed use (UDC Table 4.8-4) subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The outdoor patio referenced on your site plan appears around 2020. Site Zoning was unable to find the associated permit for this addition. Please provide the permit number for this addition. If one cannot be provided, a Development Package will be required. Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
12/31/2025 PDSD Application Completeness Express REVIEW COMPLETED