Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02329
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2026 Water - PDSD Standard APPROVED
01/22/2026 Site Landscape Standard NOT REQUIRED A full site landscape review will be completed with the DP submittal under (TD-DEV-1225-00316).

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
01/23/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/23/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please provide a list of the year and name of the adopted applicable codes from the adopting ordinance. IBC 107.2.1 For example,
2018 International Building Code (IBC)
2018 International Residential Code (IRC)
2018 International Existing Building Code (IEBC)
2009 ICC A117.1 Accessibility Code (by reference)
2018 International Mechanical Code (IMC)
2018 International Plumbing Code (IPC)
2017 National Electrical Code (NEC)
2024 International Fire Code (IFC)
2018 International Fuel Gas (IFGC)
2018 International Energy Conservation Code (IECC)
City of Tucson/Pima County Outdoor Lighting Code
2. Sheet CVR: Please amend the plans to provide a detailed description of the work involved in this permit’s scope. IBC 105.3
3. Sheet CVR: Please amend the Code Review to amend the M occupancy and include the following information.
A. Each building states all the occupancy classifications it contains. IBC 302.1
B. Buildings with more than one occupancy classification identify the mixed occupancy methodology as either accessory, nonseparated, separated, or a stated combination of types. IBC 508.1
C. Please indicate if the building has fire sprinklers Yes or No
4. Please provide a COMcheck report printed on the plan or show the following information on the plans: R-value for batt and continuous insulation with location. U-Factor, PF, and SHGC for fenestration. IECC C402.1, C407.4
5. Sheet CVR: Please amend the plans so the Sheet Index includes all the sheets in this set of construction drawings. IBC 107.2.1 For example the first sheet is labeled CVR and the Sheet Index indicates SD-1.0
6. Please provide the signed and sealed structural calculations, prepared by an Arizona licensed registrant, used in the design of this project with your next submittal. IBC 107.2.7
7. Please provide calculations showing the platform has been designed for a uniform Live Load of 100 psf. IBC Table 1607
8. Please amend the plans to show the roof structure was designed to resist the gravity load of RTU 1 IBC 107.2.7
9. Please amend the plans to provide a ramp or a lift to provide an accessible route to the Baptismal platform. IBC 1103 Keep in mind if a ramp is used the requirements of IBC Section 1012 will be put into effect.
10. Please amend the plans to provide the following information.
Provide complete wall sections for each type of wall and provide callouts for specific type of exterior wall covering, water-resistive barrier, weep screed clearance where applicable, bottom and top plate size type and number, sheathing type and thickness, stud type dimensions and spacing, insulation type and R-value, Interior wall covering. IBC 107.2.1
Exterior elevations are shown to scale for each building and structure. IBC 107.2.1
Grade plane, adjacent grade, floor, roof, and parapet heights are relatively dimensioned. IBC 107.2.1
Exterior wall coverings are identified and a reference to an installation detail is provided. IBC 1404.1
A specific exterior wall water resistive barrier is identified. IBC 1403.2
Details are referenced that show the water resistive barrier and flashing. IBC 107.2.4, 1402.2, 1404.4.
Foam plastic insulation in exterior walls meets its restrictions. IBC 2603.5
EIFS systems show an evaluation report number and provide the report. IBC 1407.2
Provide roofing details to include shingle type, underlayment and flashing. IBC 107.2.1
Details are provided that show the flashing and intersection detailing of water resistive components at dissimilar materials, corners, ends, joints, roof to wall intersection, and as otherwise needed. IBC 107.2.4
Please provide a door schedule to include door hardware. Panic hardware is required for doors serving a space with ≥ 50 persons in A. IBC 1010.1.10 The capability for free egress is specifically shown. IBC 1010.1.9
Only the main door uses the key lock option with a readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background 1010.1.9.4

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
01/09/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1225-02329 (1901 W KING AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. There are two sheets labeled E-2.0. These sheets do not provide consistent information.
a. Sight Electrical Fixtures & Schedules sheet shows multiple outdoor lighting fixtures with the wrong fixture designation.
b. Sight Electrical Fixtures & Schedules shows outdoor lighting fixtures being fed by panel A circuit A-16, while Lighting Plan sheet shows the same fixtures as being fed by both panels A & B.
2. Provide both sheets labeled E-2.0 in the sheet index and give them unique sheet designations.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/21/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02329
ADDRESS/PARCEL: (1901 W KING AV TUCSON, AZ 85713)

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2018.
2. Provide the specifications for the proposed new AC unit. The unit shall comply with Sections R403.1 and R503.1.2, IECC 2018 and shall comply with the Department of Energy efficiency requirements that went into effect on January 1, 2023.
3. Please provide an engineering evaluation, prepared by an Arizona registered design professional, verifying that the new roof structure is capable of supporting the proposed rooftop HVAC unit. Additionally, provide installation details, including the type of roof curb and attachment method and show the RTU on the building elevation views. Reference: IBC Section 107.2.7.
01/21/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02329
ADDRESS/PARCEL: (1901 W KING AV TUCSON, AZ 85713)

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide a watertight pan of galvanized steel, aluminum, or other approved material under the water heater with a drain to an approved location. Reference: Section 504.7, IPC 2018.
2. In the Water Riser diagram, the HWR appears to be connecting upstream of the expansion tank, but in the water heater detail the HWR is connecting between the expansion tank and water heater. Please correct. Reference: IBC Section 107.2.7.
3. Please show the roof drainage plan. Clarify and show on the plans where the rainwater will discharge in relation to the sidewalk. Primary rainwater leaders may not discharge onto a sidewalk. Reference: Section 7-01.4.1 E, Technical Standards Manual, Tucson Arizona Unified Development Code.
4. Show the location of all cleanouts for the building sewer on the site plan. Reference: Section 703.5, IPC 2018.
01/21/2026 Fire New Construction Standard REQUIRES RESUBMIT 1. Sheet CVR, code review. Please update your occupancy group. You have it classified as an M (mercantile). This occupancy would be considered an A3.
john.vincent@tucsonaz.gov
5203495581
01/09/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1225-02329 (1901 W KING AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
2. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
a. >>> There are two Sheets labeled E-2.0. One sheet labels outdoor lighting fixtures with designation ‘A’, while the other sheet has no designation for the fixtures. Provide consistent labeling that also matches the lumen’s calculations table.
3. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
a. >>> Calculations table on sheet E-2.0 is missing the lighting area and the chosen compliance option.
b. >>> Provide the maximum allowed lumens per Table 401.1, and the developed area of the site, and the chosen compliance option.
4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
a. >>> The calculations table on Sheet E-2.0, doesn’t include the required shielding/full-cutoff designations for the fixtures.
5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
6. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
a. >>> The Lighting Fixture table on sheet E-2.0, titled ‘Sight Electrical Fixtures & Schedules’, appears to show fixtures W1 & W2 with a color temperature of 7000K.
7. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
8. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

9. Specify any exceptions used.

10. Provide Curfew lighting controls If applicable Per section 403.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/30/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-1225-02329
Location: 1901 W KING AV
Review Date: 12/30/2025
Site Engineering Comments:
1. The proposed expansion to the site located at 1901 W KING AV falls under site work classification. Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.
2. Site Engineering is unable to approve this building permit TC-COM-1225-02329 until the Development Package has been approved by all reviewers.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
01/20/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-1225-02329
1901 W. King Ave. Tucson, AZ 85713
New Offices (1st Review)

TRANSMITTAL DATE: 1/20/2026

The site is in the R-1 zone (UDC 4.7.8). Religious Use is an allowed use in this zone (UDC Table 4.8-2).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
12/30/2025 PDSD Application Completeness Express REVIEW COMPLETED