Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1225-02322
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2026 | Commercial Building Standard | APPROVED | |||
| 04/06/2026 | Site Zoning Standard | APPROVED | |||
| 04/09/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/08/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Comment not addressed. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.] 2. Comment not addressed. [Initial comment: Clarify how the new walls and the existing ceiling system provide for return air not to use the corridors as return air ducts (i.e. do some of the walls not extend to the ceiling?).] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 03/19/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |