Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-1225-02322
Parcel: 126191900

Address:
4443 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1225-02322
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2026 Commercial Building Standard APPROVED
04/06/2026 Site Zoning Standard APPROVED
04/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/08/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Comment not addressed. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.]
2. Comment not addressed. [Initial comment: Clarify how the new walls and the existing ceiling system provide for return air not to use the corridors as return air ducts (i.e. do some of the walls not extend to the ceiling?).]
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
03/19/2026 PDSD Application Completeness Express REVIEW COMPLETED