Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1225-02309
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2026 | Commercial Plumbing Standard | APPROVED | Plumbing (P) Reviewer Andrew Bevis; abevis@safebuilt.com Discipline Status:Approved As Is Date Completed: 1/2/2026 |
||
| 01/20/2026 | Water - PDSD Standard | APPROVED | |||
| 01/20/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/26/2025 | Addressing Validation | REQUIRES RESUBMIT | Please submit a request change of address to remove the 2nd address listed on this permit, 810 W WETMORE RD TUCSON, AZ 85705. HOW TO REQUEST A CHANGE OF ADDRESS, existing permits: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf For questions: maribel.arevalo@tucsonaz.gov |
||
| 01/12/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Structural (S) Reviewer Madeline Nelson; mnelson@safebuilt.com Discipline Status:Denied Date Completed: 1/11/2026 1.General / Updates:For project updates, submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2.Sheet S001 / Design Criteria:The scope of proposed work includes the addition of a mezzanine and interior stairs. Both are being submitted as a deferred design. For coordination with the specialty engineer, please amend the structural general notes to include minimum live load requirements for these occupancies in accordance with the 2018 IBC Table 1607.1. 3.Sheet S001 / Seismic Design Criteria:The structural general notes indicate that this project falls under Seismic Design Category "B". This conflicts with the structural calculation package, Page 5, as well as the minimum seismic criteria of ASCE 7-16. Please correct the general notes to indicate Seismic Design Category "C". 4.General / Pre-Engineered Metal Buildings (for information only):The Engineer of Record has indicated that design of the pre-engineered metal building (PEMB) will be submitted as a deferred submittal. When submitting drawings for the PEMB, the following should be provided: i.All imposed design loads (dead, live equipment, etc.), seismic design data, wind design data; steel material properties and imposed loads on the foundation (both vertical and lateral). ii.Framing plans, cross sections, wall sections, floor and roof details and connections of structural members iii.A letter from the Engineer of Record stating that they have reviewed the PEMB drawings and have verified the foundation designs. Alternatively ,the EOR may stamp each sheet“approved for design concept”or similar indicating compliance with 2018 IBC Section 107.3.4. 5.Sheet S101A / Keynote M / Openings in Existing CMU:Where the scope of work includes partial demolition of existing CMU walls for new windows or doorways, the Engineer of Record must provide a detail for how the new openings are reinforced. Modifications to the existing structure do not fall under the responsibility of the specialty engineer and can not be deferred. 6.Sheet S501 / Details C5 and D6 / Concrete Piers:Details C5 and D6 indicate that masonry jambs shall be supported below grade by concrete piers. Reviewer was unable to find information on concrete pier sizes and reinforcement. Please confirm where this information has been provided. 7.General / Site Structures:Architectural site details on Sheets A104 and A105 refer to the structural drawings for information on site structures (ie. dumpster enclosure, light pole foundations, etc). Please confirm where this information has been provided or update the structural drawings to include the full scope of work. 8.General / Retaining Walls:The civil Site Improvement Plan, Sheet C-05, indicates locations of proposed retaining walls. Please provide a detail showing retaining wall height, thickness and reinforcement. 9.General / Mechanical Loads (for information only):The Mechanical Roof Plan and Mechanical Schedules on Sheets M204 and M601 indicate rooftop mechanical units exceeding 300 lb. Where these occur, their locations must be coordinated with the Prefabricated Metal Building engineer. When the PEMB drawings become available, the roof plan must include the locations and weights of RTU-5 thru RTU-9. Building (B) Reviewer Andrew Bevis; abevis@safebuilt.com Discipline Status:Approved As Is Date Completed: 1/2/2026 |
||
| 01/12/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical (E) Reviewer Ron Ross; rross@safebuilt.com Discipline Status:Denied Date Completed: 12/29/2025 1.E001 ELECTRICAL ENERGY COMPLIANCE: Need to provide an exterior lighting calculation using Tucson’s allowed Lumens per Acre calculation. 2.E206 ROOF PLAN–ELECTRICAL: Could not locate Electrical Note #4. 3.E401 ELECTRICAL ONE-LINE DIAGRAM: Feeder for Panel HL is missing a neutral conductor and cannot provide 277 Volts to function as a typical lighting panel. Panel schedule calls panel out as a 480/277 volt panel. Correct/coordinate. |
||
| 01/12/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Mechanical (M) Reviewer Jorge Valido; jvalido@safebuilt.com Discipline Status:Denied Date Completed: 1/12/2026 1.General -COMcheck Cooling BTUH Design for RTUs 5 thru 7 does not match the DX Rooftop Unit Schedule design. - 2021 IECC Section C403.3.2 HVAC equipment performance requirements. - 2015 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. 2.General -RTU 8 on Plan Sheet M203 total Supply CFM amount at the grills/diffusers does not match the DX Rooftop Unit Schedule Supply fan CFM design amount. - 2015 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. 3.General -Provide an O/A Ventilation Schedule. Specify on the drawings the outdoor air required by the 2018 IMC Section 403.3.1.1 Substantiate compliance by providing calculations on the drawings which indicate the floor area (sq. ft), maximum occupant load, minimum required ventilation rate (cfm) for each occupancy, and total ventilation rate provided to the occupied space. 4.General -Provide a sequence of operation for the CO/NO2 GAS DETECTION EQUAL TO ACME MULTIGAS CEL MODEL GAS MONITOR. - 2015 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. 5.Plan Sheet M202 -Tag identify the duct work to the RTU it belongs to. Does this duct work belong to RTU 9? Is there a vertical riser to RTU 9 which also feeds the Mezzanine - Level B? Is there a rated shaft, Fire penetrations, Fire dampers into shaft and or at floor? Provide a keynote with direction and or state on drawings. - 2015 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. |
||
| 01/07/2026 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-1225-02309 (835 W AUTO MALL DR TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code. 2. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan. 3. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. 5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. 6. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 7. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type. 8. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf 9. Specify any exceptions used. 10. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 12/31/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-1225-02309 Location: 835 W AUTO MALL DR Review Date: 12/31/2025 Site Engineering Comments: 1. Site Engineering has reviewed the building plans for compliance with development package TD-DEV-0725-00179. Until the development package is approved by all reviewers, site engineering will be unable to approve permit TC-COM-1225-02309. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 01/16/2026 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons Zoning Section Review PROJECT: TC-COM-1225-02309 - TD-DEV-0725-00179 835 W. Auto Mall Dr. Tucson, AZ 85705 Remodel and Expansion of Auto Showroom/Service Shop (1st Review) TRANSMITTAL DATE: 1/16/2026 The site is located in C-3 zone (UDC 4.7.22). Vehicle Rental and Sales are a permitted use in this zone (UDC Table 4.8-4) subject to Use Specific Standards 4.9.9.G.1 & .2. Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: Zoning has conducted a cursory review of the building permit plan set and while it appears the site plan is consistent with the associated Development Package (DP), Site Zoning cannot approve this building permit until TD-DEV-0725-00179 has been approved by all reviewers. 2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 01/16/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 12/26/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |