Permit Number: TC-COM-1225-02309
Parcel: 10408090E

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1225-02309
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2026 Commercial Building Standard APPROVED Building (B) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/2/2026

Structural (S) Reviewer
Madeline Nelson; mnelson@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 6/24/2026
06/30/2026 Commercial Electrical Standard APPROVED Electrical (E) Reviewer
Ron Ross; rross@safebuilt.com
Discipline Status:Approved with Comments
Date Completed: 6/17/2026
06/30/2026 Commercial Mechanical Standard APPROVED Mechanical (M) Reviewer
Jorge Valido; jvalido@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 6/26/2026
06/18/2026 Site Engineering Standard APPROVED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
06/17/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1225-02309 (835 W AUTO MALL DR TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The updated plans are missing the required total lumens calculation. This calculation would include only those fixtures not listed as ‘Special Use’ lighting, fixtures C-1, D-1 and WB. My calculations of the total used lumens and total allowable lumens show that this site is over the allowable lumen limit.
Total allowable: 250,000 lumens/acre × 2.34 site acres (REF sheet A000 Project Information) = 585,000 max lumens per Table 401.1, option 2.
Total used: 775,528 = (32043 * 9) + (29877 * 13) + (19768 * 5).
Total used is greater than the Total allowable.
2. Provide lumen calculations and lumen totals in compliance with Table 401.1.
06/16/2026 Addressing Validation REVIEW COMPLETED
06/16/2026 PDSD Application Completeness Express REVIEW COMPLETED