Permit Number: TC-COM-1225-02295
Parcel: 12404059A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02295
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2026 Outdoor Lighting Standard APPROVED
01/15/2026 Water - PDSD Standard APPROVED
01/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/13/2026 Commercial Building Standard REQUIRES RESUBMIT January 13, 2026
1st Review

Seaver Franks Architects
Attn: Fatima Valdez
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: KAPPA ALPHA BETA DELTA CHAPTER
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-1225-02295
Stantec Project Number: 185215066
Stantec File Number: TUC-25-113

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-2 III-B 30,672 227 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: Metal awnings.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, masonry, EFIS.

GENERAL COMMENTS

1. Please provide on the site plan(s) the following information:
a. Distance from the building to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined [2018 IBC Table 602 and Sec. 705].


ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page the kitchen hood suppression system [2018 IBC Sec. 904.12] is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. The plans indicate that metal awnings will be provided. Please either provide the documents now or list on this sheet as a deferred submittal and include the following notes:

PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.

PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.

4. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

5. The code analysis identifies the building as Type III-B construction. Per this construction type:

• Exterior bearing walls are required to have a minimum 2-hour fire-resistance rating.
• The submitted plans do not identify a listed 2-hour rated exterior bearing wall assembly for the new walls shown throughout the various project phases.
• Type III-B construction also requires exterior walls to be of noncombustible materials, with an allowance for fire-retardant-treated (FRT) wood framing and sheathing.
• While the plans indicate metal stud framing at exterior walls, the drawings do not specify that the exterior sheathing is FRT, as required.

Additionally, the plumbing plans indicate that the building is protected by an NFPA 13 automatic sprinkler system. If the building is fully sprinklered in accordance with NFPA 13 (not NFPA 13R), the construction type may be reclassified as Type V-B, which would eliminate the requirement for FRT materials and fire-resistance-rated exterior wall assemblies.
Please verify whether the building is equipped with an NFPA 13 system (not NFPA 13R) and revise the construction type and exterior wall design accordingly. [Ref. IBC 2018 Sec. 506.2 601 & 602.3]
6. Please provide listed rated through/membrane penetration firestop assemblies. [Ref. IBC 2018 Sec. 714.4.1.2]

Phase I

Sheet A2.0

1. The demolition plan indicates that the stairs to the East of the Group Study Room will be removed, however the updated floor plan on this sheet does not provide details on what will be done in place of the stairs at this location (i.e. framed in opening where stairs occurred). Please clarify and revise accordingly.

Phase II

Sheet A4.0

1. Please provide secondary (emergency overflow) roof drains for the new roof drains indicated. [Ref. IBC 2018 Sec. 1502.2]

Phase III

General

1. There are multiple instances throughout the plan-set for this phase where 1-hour fire rated walls are not indicated separating sleeping rooms from each other and other occupancies. The walls separating sleeping rooms from each other and other occupancies must be separated by 1-hour fire partitions. Please provide the listed rated assemblies for the fire partitions along with details of construction ensuring you indicate the wall terminating and the underside of the roof sheathing. If prescriptive fire resistance is being used, please be sure to include table and item number used for compliance. [Ref. IBC 2018 Sec. 420.2]

Sheet A10.3

1. Please provide a rear wall grab bar at the water closet. [Ref. ICC A117.1 – 2009 Sec. 604.5.2]

Phase IV

Sheet A2.1

1. Please provide wall type indicators for the walls at the courtyard entrance.
Sheet A2.2

1. The exterior walls of the new addition do not contain wall type indicators. Please provide.

Sheet A7.0

1. Please provide the insulation material and R-value of the floor of the addition. [Ref. IECC 2018 Sec. R402.1]

STRUCTURAL COMMENTS

General

1. Please provide the geotechnical report referenced in the structural calculations by Pattison Engineering job no. 25-0867. [Ref. IBC 2018 Sec. 1803]

MECHANICAL COMMENTS

Phase III

General

1. Please provide fire dampers at all fire partition penetrations. Multiple locations throughout the mechanical plans indicate ducts penetrating fire partitions at sleeping rooms. [Ref. IBC 2018 Sec. 717.5.4]

Sheet M1.0

1. Please provide an outdoor air balance schedule indicating all exhaust and replacement air for the facility, plus the net exfiltration, if applicable indicating the total replacement airflow rate is equal to the total exhaust rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

PLUMBING COMMENTS

Phase III

Sheet P2.0

1. The condensate trap detail is overlayed onto the Basement Enlarged Plumbing Plan. Please revise.


ELECTRICAL COMMENTS

Phase I

Sheet E2.0

1. Please provide updated short circuit current calculations for the relocated Panel SB. [Ref. NEC 2017 Art. 110]

Phase III

Sheet E2.2

1. Please provide smoke alarms in the new sleeping rooms 209, 210, 213, & 216. [Ref. IBC 2018 Sec. 420.5]

Sheet E3.0

1. Please provide updated short circuit current calculations for the relocated and new panels. [Ref. NEC 2017 Art. 110]
2.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/13/2026 Commercial Electrical Standard REQUIRES RESUBMIT January 13, 2026
1st Review

Seaver Franks Architects
Attn: Fatima Valdez
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: KAPPA ALPHA BETA DELTA CHAPTER
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-1225-02295
Stantec Project Number: 185215066
Stantec File Number: TUC-25-113

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-2 III-B 30,672 227 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: Metal awnings.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, masonry, EFIS.

GENERAL COMMENTS

1. Please provide on the site plan(s) the following information:
a. Distance from the building to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined [2018 IBC Table 602 and Sec. 705].


ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page the kitchen hood suppression system [2018 IBC Sec. 904.12] is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. The plans indicate that metal awnings will be provided. Please either provide the documents now or list on this sheet as a deferred submittal and include the following notes:

PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.

PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.

4. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

5. The code analysis identifies the building as Type III-B construction. Per this construction type:

• Exterior bearing walls are required to have a minimum 2-hour fire-resistance rating.
• The submitted plans do not identify a listed 2-hour rated exterior bearing wall assembly for the new walls shown throughout the various project phases.
• Type III-B construction also requires exterior walls to be of noncombustible materials, with an allowance for fire-retardant-treated (FRT) wood framing and sheathing.
• While the plans indicate metal stud framing at exterior walls, the drawings do not specify that the exterior sheathing is FRT, as required.

Additionally, the plumbing plans indicate that the building is protected by an NFPA 13 automatic sprinkler system. If the building is fully sprinklered in accordance with NFPA 13 (not NFPA 13R), the construction type may be reclassified as Type V-B, which would eliminate the requirement for FRT materials and fire-resistance-rated exterior wall assemblies.
Please verify whether the building is equipped with an NFPA 13 system (not NFPA 13R) and revise the construction type and exterior wall design accordingly. [Ref. IBC 2018 Sec. 506.2 601 & 602.3]
6. Please provide listed rated through/membrane penetration firestop assemblies. [Ref. IBC 2018 Sec. 714.4.1.2]

Phase I

Sheet A2.0

1. The demolition plan indicates that the stairs to the East of the Group Study Room will be removed, however the updated floor plan on this sheet does not provide details on what will be done in place of the stairs at this location (i.e. framed in opening where stairs occurred). Please clarify and revise accordingly.

Phase II

Sheet A4.0

1. Please provide secondary (emergency overflow) roof drains for the new roof drains indicated. [Ref. IBC 2018 Sec. 1502.2]

Phase III

General

1. There are multiple instances throughout the plan-set for this phase where 1-hour fire rated walls are not indicated separating sleeping rooms from each other and other occupancies. The walls separating sleeping rooms from each other and other occupancies must be separated by 1-hour fire partitions. Please provide the listed rated assemblies for the fire partitions along with details of construction ensuring you indicate the wall terminating and the underside of the roof sheathing. If prescriptive fire resistance is being used, please be sure to include table and item number used for compliance. [Ref. IBC 2018 Sec. 420.2]

Sheet A10.3

1. Please provide a rear wall grab bar at the water closet. [Ref. ICC A117.1 – 2009 Sec. 604.5.2]

Phase IV

Sheet A2.1

1. Please provide wall type indicators for the walls at the courtyard entrance.
Sheet A2.2

1. The exterior walls of the new addition do not contain wall type indicators. Please provide.

Sheet A7.0

1. Please provide the insulation material and R-value of the floor of the addition. [Ref. IECC 2018 Sec. R402.1]

STRUCTURAL COMMENTS

General

1. Please provide the geotechnical report referenced in the structural calculations by Pattison Engineering job no. 25-0867. [Ref. IBC 2018 Sec. 1803]

MECHANICAL COMMENTS

Phase III

General

1. Please provide fire dampers at all fire partition penetrations. Multiple locations throughout the mechanical plans indicate ducts penetrating fire partitions at sleeping rooms. [Ref. IBC 2018 Sec. 717.5.4]

Sheet M1.0

1. Please provide an outdoor air balance schedule indicating all exhaust and replacement air for the facility, plus the net exfiltration, if applicable indicating the total replacement airflow rate is equal to the total exhaust rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

PLUMBING COMMENTS

Phase III

Sheet P2.0

1. The condensate trap detail is overlayed onto the Basement Enlarged Plumbing Plan. Please revise.


ELECTRICAL COMMENTS

Phase I

Sheet E2.0

1. Please provide updated short circuit current calculations for the relocated Panel SB. [Ref. NEC 2017 Art. 110]

Phase III

Sheet E2.2

1. Please provide smoke alarms in the new sleeping rooms 209, 210, 213, & 216. [Ref. IBC 2018 Sec. 420.5]

Sheet E3.0

1. Please provide updated short circuit current calculations for the relocated and new panels. [Ref. NEC 2017 Art. 110]
2.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/13/2026 Commercial Mechanical Standard REQUIRES RESUBMIT January 13, 2026
1st Review

Seaver Franks Architects
Attn: Fatima Valdez
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: KAPPA ALPHA BETA DELTA CHAPTER
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-1225-02295
Stantec Project Number: 185215066
Stantec File Number: TUC-25-113

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-2 III-B 30,672 227 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: Metal awnings.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, masonry, EFIS.

GENERAL COMMENTS

1. Please provide on the site plan(s) the following information:
a. Distance from the building to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined [2018 IBC Table 602 and Sec. 705].


ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page the kitchen hood suppression system [2018 IBC Sec. 904.12] is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. The plans indicate that metal awnings will be provided. Please either provide the documents now or list on this sheet as a deferred submittal and include the following notes:

PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.

PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.

4. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

5. The code analysis identifies the building as Type III-B construction. Per this construction type:

• Exterior bearing walls are required to have a minimum 2-hour fire-resistance rating.
• The submitted plans do not identify a listed 2-hour rated exterior bearing wall assembly for the new walls shown throughout the various project phases.
• Type III-B construction also requires exterior walls to be of noncombustible materials, with an allowance for fire-retardant-treated (FRT) wood framing and sheathing.
• While the plans indicate metal stud framing at exterior walls, the drawings do not specify that the exterior sheathing is FRT, as required.

Additionally, the plumbing plans indicate that the building is protected by an NFPA 13 automatic sprinkler system. If the building is fully sprinklered in accordance with NFPA 13 (not NFPA 13R), the construction type may be reclassified as Type V-B, which would eliminate the requirement for FRT materials and fire-resistance-rated exterior wall assemblies.
Please verify whether the building is equipped with an NFPA 13 system (not NFPA 13R) and revise the construction type and exterior wall design accordingly. [Ref. IBC 2018 Sec. 506.2 601 & 602.3]
6. Please provide listed rated through/membrane penetration firestop assemblies. [Ref. IBC 2018 Sec. 714.4.1.2]

Phase I

Sheet A2.0

1. The demolition plan indicates that the stairs to the East of the Group Study Room will be removed, however the updated floor plan on this sheet does not provide details on what will be done in place of the stairs at this location (i.e. framed in opening where stairs occurred). Please clarify and revise accordingly.

Phase II

Sheet A4.0

1. Please provide secondary (emergency overflow) roof drains for the new roof drains indicated. [Ref. IBC 2018 Sec. 1502.2]

Phase III

General

1. There are multiple instances throughout the plan-set for this phase where 1-hour fire rated walls are not indicated separating sleeping rooms from each other and other occupancies. The walls separating sleeping rooms from each other and other occupancies must be separated by 1-hour fire partitions. Please provide the listed rated assemblies for the fire partitions along with details of construction ensuring you indicate the wall terminating and the underside of the roof sheathing. If prescriptive fire resistance is being used, please be sure to include table and item number used for compliance. [Ref. IBC 2018 Sec. 420.2]

Sheet A10.3

1. Please provide a rear wall grab bar at the water closet. [Ref. ICC A117.1 – 2009 Sec. 604.5.2]

Phase IV

Sheet A2.1

1. Please provide wall type indicators for the walls at the courtyard entrance.
Sheet A2.2

1. The exterior walls of the new addition do not contain wall type indicators. Please provide.

Sheet A7.0

1. Please provide the insulation material and R-value of the floor of the addition. [Ref. IECC 2018 Sec. R402.1]

STRUCTURAL COMMENTS

General

1. Please provide the geotechnical report referenced in the structural calculations by Pattison Engineering job no. 25-0867. [Ref. IBC 2018 Sec. 1803]

MECHANICAL COMMENTS

Phase III

General

1. Please provide fire dampers at all fire partition penetrations. Multiple locations throughout the mechanical plans indicate ducts penetrating fire partitions at sleeping rooms. [Ref. IBC 2018 Sec. 717.5.4]

Sheet M1.0

1. Please provide an outdoor air balance schedule indicating all exhaust and replacement air for the facility, plus the net exfiltration, if applicable indicating the total replacement airflow rate is equal to the total exhaust rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

PLUMBING COMMENTS

Phase III

Sheet P2.0

1. The condensate trap detail is overlayed onto the Basement Enlarged Plumbing Plan. Please revise.


ELECTRICAL COMMENTS

Phase I

Sheet E2.0

1. Please provide updated short circuit current calculations for the relocated Panel SB. [Ref. NEC 2017 Art. 110]

Phase III

Sheet E2.2

1. Please provide smoke alarms in the new sleeping rooms 209, 210, 213, & 216. [Ref. IBC 2018 Sec. 420.5]

Sheet E3.0

1. Please provide updated short circuit current calculations for the relocated and new panels. [Ref. NEC 2017 Art. 110]
2.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/13/2026 Commercial Plumbing Standard REQUIRES RESUBMIT January 13, 2026
1st Review

Seaver Franks Architects
Attn: Fatima Valdez
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: KAPPA ALPHA BETA DELTA CHAPTER
REMODEL AND ADDITION

City of Tucson Permit Number: TC-COM-1225-02295
Stantec Project Number: 185215066
Stantec File Number: TUC-25-113

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-2 III-B 30,672 227 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: Metal awnings.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, structural steel, high-strength bolts, field welding, masonry, EFIS.

GENERAL COMMENTS

1. Please provide on the site plan(s) the following information:
a. Distance from the building to the lot lines and/or adjacent buildings on the same lot, so that fire separation distance, rating of exterior walls, protection of openings and projections can be determined [2018 IBC Table 602 and Sec. 705].


ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page the kitchen hood suppression system [2018 IBC Sec. 904.12] is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. The plans indicate that metal awnings will be provided. Please either provide the documents now or list on this sheet as a deferred submittal and include the following notes:

PER IBC Section 107.3.4
<Name of Registrant>, the registered design professional in charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building.

PER IBC Section 107.3.4.1
Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge, who shall review them and forward them to the Building Official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance with the design of the building.

4. Please provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

5. The code analysis identifies the building as Type III-B construction. Per this construction type:

• Exterior bearing walls are required to have a minimum 2-hour fire-resistance rating.
• The submitted plans do not identify a listed 2-hour rated exterior bearing wall assembly for the new walls shown throughout the various project phases.
• Type III-B construction also requires exterior walls to be of noncombustible materials, with an allowance for fire-retardant-treated (FRT) wood framing and sheathing.
• While the plans indicate metal stud framing at exterior walls, the drawings do not specify that the exterior sheathing is FRT, as required.

Additionally, the plumbing plans indicate that the building is protected by an NFPA 13 automatic sprinkler system. If the building is fully sprinklered in accordance with NFPA 13 (not NFPA 13R), the construction type may be reclassified as Type V-B, which would eliminate the requirement for FRT materials and fire-resistance-rated exterior wall assemblies.
Please verify whether the building is equipped with an NFPA 13 system (not NFPA 13R) and revise the construction type and exterior wall design accordingly. [Ref. IBC 2018 Sec. 506.2 601 & 602.3]
6. Please provide listed rated through/membrane penetration firestop assemblies. [Ref. IBC 2018 Sec. 714.4.1.2]

Phase I

Sheet A2.0

1. The demolition plan indicates that the stairs to the East of the Group Study Room will be removed, however the updated floor plan on this sheet does not provide details on what will be done in place of the stairs at this location (i.e. framed in opening where stairs occurred). Please clarify and revise accordingly.

Phase II

Sheet A4.0

1. Please provide secondary (emergency overflow) roof drains for the new roof drains indicated. [Ref. IBC 2018 Sec. 1502.2]

Phase III

General

1. There are multiple instances throughout the plan-set for this phase where 1-hour fire rated walls are not indicated separating sleeping rooms from each other and other occupancies. The walls separating sleeping rooms from each other and other occupancies must be separated by 1-hour fire partitions. Please provide the listed rated assemblies for the fire partitions along with details of construction ensuring you indicate the wall terminating and the underside of the roof sheathing. If prescriptive fire resistance is being used, please be sure to include table and item number used for compliance. [Ref. IBC 2018 Sec. 420.2]

Sheet A10.3

1. Please provide a rear wall grab bar at the water closet. [Ref. ICC A117.1 – 2009 Sec. 604.5.2]

Phase IV

Sheet A2.1

1. Please provide wall type indicators for the walls at the courtyard entrance.
Sheet A2.2

1. The exterior walls of the new addition do not contain wall type indicators. Please provide.

Sheet A7.0

1. Please provide the insulation material and R-value of the floor of the addition. [Ref. IECC 2018 Sec. R402.1]

STRUCTURAL COMMENTS

General

1. Please provide the geotechnical report referenced in the structural calculations by Pattison Engineering job no. 25-0867. [Ref. IBC 2018 Sec. 1803]

MECHANICAL COMMENTS

Phase III

General

1. Please provide fire dampers at all fire partition penetrations. Multiple locations throughout the mechanical plans indicate ducts penetrating fire partitions at sleeping rooms. [Ref. IBC 2018 Sec. 717.5.4]

Sheet M1.0

1. Please provide an outdoor air balance schedule indicating all exhaust and replacement air for the facility, plus the net exfiltration, if applicable indicating the total replacement airflow rate is equal to the total exhaust rate plus the net exfiltration. [Ref. IMC 2018 Sec. 508.1.2]

PLUMBING COMMENTS

Phase III

Sheet P2.0

1. The condensate trap detail is overlayed onto the Basement Enlarged Plumbing Plan. Please revise.


ELECTRICAL COMMENTS

Phase I

Sheet E2.0

1. Please provide updated short circuit current calculations for the relocated Panel SB. [Ref. NEC 2017 Art. 110]

Phase III

Sheet E2.2

1. Please provide smoke alarms in the new sleeping rooms 209, 210, 213, & 216. [Ref. IBC 2018 Sec. 420.5]

Sheet E3.0

1. Please provide updated short circuit current calculations for the relocated and new panels. [Ref. NEC 2017 Art. 110]
2.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/14/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
12/31/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-1225-02295
Location: 1050 N MOUNTAIN AV
Review Date: 12/31/2025
Site Engineering Comments:
1. Site Engineering has reviewed the building plans for compliance with development package TD-DEV-1025-00270. Until the development package is approved by all reviewers, site engineering will be unable to approve permit TC-COM-1225-02295.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
01/13/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-1225-02295 - TD-DEV-1025-00270
1050 N. Mountain Ave. Tucson, AZ 85719
Minor Building Expansion and Reconfiguration of Parking Areas (1st Review)

TRANSMITTAL DATE: 1/13/2026

The site is located in R-3 zone (UDC 4.7.22). Group Dwelling is a permitted use in this zone (UDC Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Zoning has conducted a cursory review of the building permit plan set and while it appears the site plan is consistent with the associated Development Package (DP), Site Zoning cannot approve this building permit until TD-DEV-1025-00270 has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
12/22/2025 PDSD Application Completeness Express REVIEW COMPLETED