Permit Number: TC-COM-1225-02291
Parcel: 130144440

Address:
3950 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02291
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2026 Commercial Electrical Standard APPROVED
01/16/2026 Commercial Mechanical Standard APPROVED
01/16/2026 Commercial Plumbing Standard APPROVED
01/14/2026 Site Zoning Standard APPROVED Interior TI w/ minor ADA upgrades
01/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/15/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02291
ADDRESS: (3950 E 22ND ST TUCSON, AZ 85711)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

COMMENTS:
1. SHEET A0.1
a. BUILDING CODES
i. Please add the following codes:
1. 2018 International Fuel Gas Code
2. 2018 International Mechanical Code
3. 2018 International Plumbing Code
4. 2018 International Energy Conservation Code
2. FLOOR PLAN
i. Clear aisle dimension between corner of freezer to the katicorner equipment.
1. Code required dimension is not met.
2. The clear dimension with occupant load of 50 or more is not less than 44 inches per IBC Table 1020.3.
3. Please correct this discrepancy.
3. WOMEN’S RESTROOM
a. The women’s restroom is not compliant.
i. 604.3.3 No other fixtures (lavatory) or obstructions shall be within the required water closet clearance. FIGURE 604.3
ii. Clearance width around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall per ICC A117.1 sec 604.3.1
iii. 604.3.2 Clearance depth around the water closet shall be 56 inches minimum in depth, measured perpendicular from the rear wall.
4. SIGN
a. Please add the following note:
i. Please submit a separate sign permit for any signs associated with this project.
5. Please resubmit.
Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
12/24/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-1225-02291
Location: 3950 E 22ND ST
Review Date: 12/24/2025
Site Engineering Comments:
1. This property/site is located within the XS100-year FEMA floodplain section of the Naylor wash within the Tucson Arroyo Watershed. Due to the floodplain, it will be required that a flood plain use (FPU) permit be submitted for review and approval for substantial improvement calculations.
2. It should be noted that the FPU permit is an entirely separate permit that can be applied and submitted for within the “Sub-Records” tab of this commercial permit within TDC Online. For the FPU submission, please provide all construction documents related to the scope of work provided similarly as the commercial permit.
3. For the FPU permit please submit a cost estimate form that will break down the total cost into separate lines, separating labor, materials/equipment, and warranties/fees associated with the project. Ensure to have company/contractor letterhead on the document for proper documentation. This cost estimate will be used for substantial improvement calculations. The cost estimate should not include any site work related costs such as landscaping, parking area, etc.
4. It is required that the FPU permit be reviewed and approved prior to Site Engineering approval to permit TC-COM-1225-02291.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
01/13/2026 Fire New Construction Standard REVIEW COMPLETED
12/22/2025 PDSD Application Completeness Express REVIEW COMPLETED