Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1225-02287
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2026 | Commercial Electrical Standard | APPROVED | |||
| 03/10/2026 | Commercial Mechanical Standard | APPROVED | |||
| 03/13/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/17/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions regarding this review, please contact Drew Szentesy at Drew.Szentesy@tucsonaz.gov or the team at PDSD-Permits@tucsonaz.gov The address has unit numbers attached to it in our system. Please submit a change of address request through sub records to add the unit number to the permit location. Also please include the unit number on the construction plans. For help navigating sub records: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf |
||
| 03/13/2026 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1225-02287 ADDRESS/PARCEL: (5431 E WILLIAMS BL TUCSON, AZ 85711) TC-DMO-0226-00038 (4515 E 22ND ST TUCSON, AZ 857 Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. COMMENTS: 1. NONE of the responses to the comments are reflected in the submitted drawings. a. For example: i. Sheet 501, response says it has been added. The Sheet Index does not contain Sheet 501. The actual Sheet 501 is not present within the set of actual drawings. ii. Means of egress requested information were not corrected. iii. Etc. iv. Please look over every comments and make sure your responses are actually 2. Please resubmit. |
||
| 03/10/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1225-02287 ADDRESS/PARCEL: 5431 E WILLIAMS BL TUCSON, AZ 85711Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Previous comment not addressed. Please include the minimum plumbing facilities required in the Code Data section on sheet A-100. [Previous comment - Provide calculations to verify that the minimum plumbing facilities required by Table 2902.1, IBC 2018, for the suite have been provided. Reference: Sections 1109.5 and 2902.1, IBC 2018.] |
||
| 03/10/2026 | Water - PDSD Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1225-02287 ADDRESS/PARCEL: 5431 E WILLIAMS BL TUCSON, AZ 85711Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Previous comment not fully addressed. Please show the size of the water meter and show the total water demand served by the meter on the plans. [Previous comment - Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand that will be served by the water meter. Reference: Section 107.2.1, IBC 2018.] |
||
| 03/10/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 02/17/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |