Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2026 Site Zoning Standard APPROVED Interior TI Only. Ref: TZ-CMP-0325-00040
01/02/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/22/2025 Site Engineering Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
01/07/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1225-02287 (5431 E WILLIAMS BL TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Show or notate that the ‘Water Treatment’ area shall meet the requirements of NEC 300.6 for Protection Against Corrosion and Deterioration.
2. Show or notate special electrical requirements as required by NEC 517. Note the location of Patient Care Space and category.
3. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck).


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/13/2026 Fire New Construction Standard REQUIRES RESUBMIT -Sheet A-100, code data. Please include fire alarm information in the code data. Building will need a fire alarm per 2024 IFC 907.2.2, 907.2.2.1.
john.vincent@tucsonaz.gov
5203495581
12/22/2025 PDSD Application Completeness Express REVIEW COMPLETED