Permit Number: TC-COM-1225-02287
Parcel: 12810078E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02287
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2026 Site Zoning Standard APPROVED Interior TI Only. Ref: TZ-CMP-0325-00040
01/02/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/22/2025 Site Engineering Standard NOT REQUIRED
01/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/15/2026 Addressing Validation REQUIRES RESUBMIT Please contact Pima County Addressing to resolve issue. Addressing@pima.gov or 520-724-9512
Please provide suite number for this project on the cover sheet and in the Title Block of each sheet of the construction documents.
01/15/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend the plans to confirm this facility is in operation for less than 24 hours a day and is an Outpatient Ambulatory Care use. IBC 304.1
2. Please update the code data to indicate the floor number of the building for this proposed tenant improvement. IBC 107.2.1
3. Please amend the plans to indicate the address and suite number on the cover sheet and the title block. IBC 107.2.1
4. Please amend the plans to provide a wall assembly section drawing for each wall type to include connections, width, stud spacing, wall height, wall covering, insulation, . For metal stud walls, for interior walls and partitions that exceed 6 feet in height, including their finish materials, demonstrate adequate strength and stiffness to resist the loads to which they are subjected but not less than a horizontal load of 5 psf IBC 1607.15 For example provide metal stud table or provide calculations to show compliance.
5. Please amend the plans to provide the following Fire-Resistance information.
A. Provide details of the fire-resistance rated walls, floors. The entire figure assembly is shown on the drawings. Identify the origin of the assembly and any number it is assigned. IBC 703.3
B. Provide details showing the vertical continuity of fire barriers, fire partitions, smoke barriers, and smoke partitions are provided. IBC 706.5, 706.6, 707.5, 708.4, 709.4, 710.4
C. Provide details for penetration firestops. The entire assembly is shown on the drawings. IBC 714.1
6. Sheet A-901: Please provide the following Means of Egress information. IBC 107.2.3
A. The number of occupants is shown for every room and space on the egress plan. IBC 107.2.3
B. The number of occupants being served by each egress door is shown. IBC 107.2.3
C. The size of each egress door is shown and is compared to allowable. IBC 1005.3
D. The exit access travel distance is dimensioned with a clear start and stop point. IBC 1017.2
E. The common path of egress travel is dimensioned with a clear start and stop point. IBC 1006.2.1

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
01/07/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1225-02287 (5431 E WILLIAMS BL TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Show or notate that the ‘Water Treatment’ area shall meet the requirements of NEC 300.6 for Protection Against Corrosion and Deterioration.
2. Show or notate special electrical requirements as required by NEC 517. Note the location of Patient Care Space and category.
3. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck).


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/20/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
01/20/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
2. Provide calculations to verify that the minimum plumbing facilities required by Table 2902.1, IBC 2018, for the suite have been provided. Reference: Sections 1109.5 and 2902.1, IBC 2018.
3. Provide a specification for BFP-1and show that it is being installed per the manufacturer’s instructions. Reference: Section 303.2, IPC 2018.
4. Show the cleanout locations for the drain and for the vent piping for the island vent sinks and lavatories. Reference: Sections 708.1.1 and 916.3, IPC 2018.
01/13/2026 Fire New Construction Standard REQUIRES RESUBMIT -Sheet A-100, code data. Please include fire alarm information in the code data. Building will need a fire alarm per 2024 IFC 907.2.2, 907.2.2.1.
john.vincent@tucsonaz.gov
5203495581
01/20/2026 Water - PDSD Standard REQUIRES RESUBMIT Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand that will be served by the water meter. Reference: Section 107.2.1, IBC 2018.
12/22/2025 PDSD Application Completeness Express REVIEW COMPLETED