Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1225-02283
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/18/2025 | Addressing Validation | REQUIRES RESUBMIT | Plans submitted missing complete project address and location of work. Please resubmit plans and include the complete project address and location of work. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: maribel.arevalo@tucsonaz.gov | ||
| 12/18/2025 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1225-02283 (103 N PANTANO RD TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). Electrical Review: Plans shall include (as necessary for scope of work), but may not be limited to items below: 1. Provide an electrical demo plan for any demo’ed electrical or appliances. 2. Provide electrical load calculations, for the Main Panels, Per NEC 220.40, demonstrating the existing electrical system can support the additional load. 3. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. 4. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. 5. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number. 6. Show all GFCI protection (NEC 210.8(B)) in readily accessible location per NEC 210.8. Additional comments may be forthcoming with complete electrical plans for the building and site. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 12/18/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |