Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02282
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2026 Commercial Electrical Standard APPROVED
01/12/2026 Site Zoning Standard APPROVED Interior TI ONLY
01/02/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/19/2025 Site Engineering Standard NOT REQUIRED
01/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/12/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide permit number for Reference to Approved Shell Plans. For 1st Tenant Improvement, shell permit number shall be referenced in plan set. Per Commercial Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Please amend the plans to update the number of occupants as the occupant load of 50 does not appear to reflect the actual occupant load of this building space. IBC 1004.1 For example the waiting area is around 900sf and would have about 70 occupants according to the furniture plan on sheet E4.
3. Please amend the waiting lobby exiting plan as two exits are required for this space as more than 49 occupants are in this space. IBC Table 1006.2.1 Keep in mind that exits and exit access components are separated by 1/3rd the distance of the space. IBC 1007.1
4. Please amend the plans to provide an egress plan/life safety plan using the same scale as the floor plan. IBC 107.2.3 and showing the following information.
A. The exit access travel distance is dimensioned with a clear start and stop point. IBC 1017.2
B. The exit access travel distance is dimensioned with a clear start and stop point. IBC 1017.2 For example, it appears in some areas/rooms, the exit signs are not visible when leaving the room.
C. Indicate the number of occupants, occupant load factor and square footage for each area, and room.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
01/14/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02282
ADDRESS/PARCEL: (1707 W SAINT MARYS RD Unit:UNIT 235 TUCSON, AZ 85745)
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:

1. Please provide more information about the exhaust system. Please amend the plans to include this information. Reference: IMC 2018, Section 503.1.
a. Exhaust equipment schedule
b. Location of exhaust outlets
c. How are the return air boots are tied into the existing system (Detail 1/M2.0)
2. Please clarify why the required exhaust ventilation for the restrooms is shown as zero in the outdoor air calculation table. Reference: IMC 2018, Table 403.3.1.1
01/14/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02282
ADDRESS/PARCEL: (1707 W SAINT MARYS RD Unit:UNIT 235 TUCSON, AZ 85745)
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:

1. Please provide details of the connection of the condensate line to the tailpiece fitting at the sink/lavatory. Show how it complies with section 802.1.5 of the 2018 IPC.
01/14/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02282
ADDRESS/PARCEL: (1707 W SAINT MARYS RD Unit:UNIT 235 TUCSON, AZ 85745)
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:

1. In the water demand calcs, please provide the total water demand served by the 2” water meter to verify that it can accommodate the new fixture demand. Reference: IBC 2018, Section 107.2.1.
01/12/2026 Fire New Construction Standard REVIEW COMPLETED
12/19/2025 PDSD Application Completeness Express REVIEW COMPLETED