Permit Number: TC-COM-1225-02281
Parcel: 13316025C

Address:
2180 N WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02281
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2026 Commercial Electrical Standard APPROVED
01/12/2026 Commercial Mechanical Standard APPROVED
01/13/2026 Site Zoning Standard APPROVED
01/13/2026 Water - PDSD Standard APPROVED
01/02/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/19/2025 Site Engineering Standard NOT REQUIRED
01/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/12/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Sheet G2.0: Please amend the Project Information to indicate City of Tucson as the Jurisdiction.
2. Sheet G2.0: Please change the door swing so the exit door swings in the direction of egress as doors serving a space with ≥ 50 persons shall swing in the direction of egress travel. IBC 1010.1.2.1 For example, the exit door at Reception room #100.
3. Provide illumination for the means of egress, including the exit discharge per IBC 1008. Show compliance with the following:
A. The means of egress shall be illuminated at all times the building space is occupied.
B. The means of egress illumination level shall not be less than 1 foot-candle at the walking surface.
C. The means of egress illumination shall be supplied by backup power (consisting of storage batteries, unit equipment, or an on-site generator) for a duration of not less than 90 minutes. IBC 1008.3
4. Please add exit signs as necessary, as required to direct egress, and every 100 feet. IBC 1013.1 For example, It appears that some more exit signage is necessary as the occupants exit the areas near the break room.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
01/13/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02281
ADDRESS/PARCEL: (2180 N WILMOT RD TUCSON, AZ 85712)
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

COMMENTS:

1. Sinks are not permitted to serve as drinking fountains, and no other drinking fountain is shown on the drawings. Drinking fountains shall be provided in accordance with the minimum plumbing fixture requirements of the code. Revise the plans to indicate a code-compliant drinking fountain or water dispenser. (IBC 2018, Section 2902)
01/12/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
12/19/2025 PDSD Application Completeness Express REVIEW COMPLETED