Permit Number: TC-COM-1225-02250
Parcel: 141432830

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02250
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/31/2025 Commercial Electrical Standard APPROVED
12/26/2025 Site Engineering Standard NOT REQUIRED
01/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/09/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02250
ADDRESS: (6685 E CAMINO ESTARNA TUCSON, AZ 85756)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

COMMENTS:
1. SHEET A1
a. Building Code Information
i. Occupancy Classification
1. The ADHS License Application shows the applicant as IMMANUEL ASSISTED LIVING LLC.
2. Your Code Information shows a category that is available within the ADHS License Application: BEHAVIORAL HEALTH RESIDENTIAL FACILITY A.A.C. R9-10-101(36) AND A.A.C. TITLE 9, CHAPTER 10, ARTICLE 7.
3. On page 2 of 12 of the ADHS License Application, your client selected: ASSISTED LIVING Home.
4. The confusion above require correction.
5. Please enter the correct Occupancy Classification.
ii. Construction Type
1. The Google Street View shows home as having stucco exterior finish.
2. With the above in mind, shouldn’t this structure be a VB. (Your drawing shows IIIB)
b. Fire Safety Legend
i. Emergency Light / Exit Sign
1. Please specify that they are to have battery backup.
c. Code Editions
i. Please add: ICC A117.1 - 2017 Accessible and Usable Building and Facilities.
d. Project Description
i. No Proposed work?
1. Since remodeling is occurring in this structure, please correct this.
e. Water Closet clear floor area.
i. No other fixtures or obstructions shall be within the required water closet clearance. ICC A117.1 section 604.3.3 figure 604.3
ii. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. ICC A117.1 section 604.3.1
iii. Clearance around the water closet shall be 56 inches minimum in depth, measured perpendicular from the rear wall. ICC A117.1 section 604.3.2
iv. Your lavatory is located within the water closer floor clearance.
1. Please correct this non-compliance.
f. Roll-in-shower(s) -or- Bathtub(s)
i. Please confirm whether Bedrooms 3 and 7 have roll-in-showers.
ii. Please indicate on the floor plan.
iii. Lavatory in front shower.
1. Please make sure to comply to ICC A117.1 figure 608.2.2.2
g. Lavatory
i. Lavatory shall be maximum 34 inches above floor to the higher of the rim or counter surface, faucets and soap dispenser shall have a reach depth of 11 inches per ANSI 606.5
ii. Metered faucets shall remain open for 10 seconds minimum per ANSI 606.4
iii. Water supply and drain pipes under lavatories shall be insulated to protect against contact per ANSI 606.6
iv. Please indicate the above on your drawing.
2. Please resubmit.
Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
01/08/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02250
ADDRESS/PARCEL: (6685 E CAMINO ESTARNA TUCSON, AZ 85756)
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

COMMENTS:
1. The water heater is shown installed in a prohibited location. Please revise the plans to demonstrate compliance with Section 303.3(5) of the 2018 IFGC, or relocate the appliance as required.
2. Combustion air shall be provided directly from the outdoors in accordance with Section 304.6 of the 2018 IFGC. Please show the combustion air source and method on the plans.
3. It appears the mini-split cassette may interfere with the water heater access door. Demonstrate that required access and service clearances are maintained in accordance with Section 306.2 of the 2018 IFGC.
4. Air conditioner schedule shows AC 1 instead of AC 2. Please correct.
5. The mini-split outdoor condensing unit is shown between Bedrooms 5 and 6 in the Manual J calculations; however, on the plans it is shown installed near Bathroom 1 on Sheet A5. Please clarify the proposed location of the mini-split outdoor condensing unit and revise the plans for consistency.
6. Also, please clarify/provide details for the mounting and support of the mini-split outdoor condensing unit on the plans, in accordance with IBC 2018 Section 107.2.1.
01/13/2026 Site Zoning Standard REQUIRES RESUBMIT 1. COMMENT: Correct the zoning on this plan from "RX-2" to "PAD-7".
2. COMMENT: Provide a general note that indicates a zoning use for this property (which is different that the building code occupancy type). Per the UDC, the zoning use is "Adult and Behavioral Health Service, Maximum 10 Residents, subject to use-specific standards 4.9.7.J. 2.a, 3.a, 4".
3. COMMENT: Provide a general note that indicates what the Arizona Department of Health Services application class for this use is. This use should correspond with the application class type selected for the ADHS application online.
4. COMMENT: Per UDC TABLE 7.4.4-1, the minimum required number of parking spaces on site is four. Clearly demonstrate that four parking spaces are able to be parked on site. A typical parking space is 8.5' x 18'. Tandem parking is permissible.

Contact Fernando Garcia, Lead Planner, Site Zoning at fernando.garcia2@tucsonaz.gov.
01/06/2026 Fire New Construction Standard REVIEW COMPLETED
12/17/2025 PDSD Application Completeness Express REVIEW COMPLETED