Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1225-02247
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2026 | Commercial Building Standard | APPROVED | |||
| 02/10/2026 | Commercial Mechanical Standard | APPROVED | |||
| 02/12/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/10/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1225-02247 ADDRESS/PARCEL: 4373 E SPEEDWAY BL TUCSON, AZ 85712 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Please show a detail on the drawing of how the drain for the waterdrop reverse osmosis unit is being installed. The Product User Manual shows a drain saddle and saddle-type fittings are prohibited. Reference: Section 707.1 (6), IPC 2018. 2. Provide accessible cleanouts in the island sink vent system to permit rodding of all portions of the vents located below the flood rim of the fixture. Reference: Section 916.3, IPC 2018. |
||
| 01/23/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |