Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-1225-02247
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/10/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Show how the island fixture vent is to be installed for sink S-1 on the floor plan, considering that there is no island. Reference: Section 107.2.1, IBC 2018. [Initial comment: Explain how the trap for sink S-1 has been vented in accordance with one of the methods shown in the IPC. Reference: Sections 901.2.1 and 916.3, IPC 2018.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 03/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |