Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1225-02242
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/23/2026 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1225-02242 ADDRESS: 1702 E SPEEDWAY BL TUCSON, AZ 85719 Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. COMMENTS: The original comments were not responded to. They have been copied and pasted below. Please respond along with your response letter as requested above. 1. STRUCTURAL CALCULATION a. Please submit the structural calculation generated by an Arizona Licensed Structural Engineer with the affixed seal/signature/date. i. This should include the analysis of the existing structure carrying this hood. ii. This should include the steel beam sizing that is called within the drawing. iii. Please submit the detail drawings by the same engineer. 1. Please submit detail drawings on the hood structural framing. 2. Please show the detail at the roof level. 2. ANSUL SYSTEM a. Please provide information on the ansul system and layout of the nozzles. 3. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. |
||
| 03/24/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Comment not resolved. Provide structural calculations to show that the proposed hood supports are adequate. [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.] 2. The supply plenum is not shown on drawings. Provide verification of adequate make up air: 2520 CFM needed through the supply plenum plus an additional 650 CFM from the space. [Initial comment: Verify that adequate make-up air is being provided for the kitchen exhaust hood. Reference: Section 508.1 IMC 2018.]. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 03/03/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |