Permit Number: TC-COM-1225-02242
Parcel: 12402026A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02242
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2025 Commercial Electrical Standard APPROVED
01/07/2026 Commercial Plumbing Standard NOT REQUIRED
12/17/2025 Site Engineering Standard NOT REQUIRED
01/07/2026 Site Zoning Standard NOT REQUIRED
01/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/05/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02242
ADDRESS: 1702 E SPEEDWAY BL TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.


COMMENTS:
1. STRUCTURAL CALCULATION
a. Please submit the structural calculation generated by an Arizona Licensed Structural Engineer with the affixed seal/signature/date.
i. This should include the analysis of the existing structure carrying this hood.
ii. This should include the steel beam sizing that is called within the drawing.
iii. Please submit the detail drawings by the same engineer.
1. Please submit detail drawings on the hood structural framing.
2. Please show the detail at the roof level.
2. ANSUL SYSTEM
a. Please provide information on the ansul system and layout of the nozzles.
3. Please resubmit.
Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
01/07/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.
2. Assuming that the existing grease ducts are being reused, provide the dimensions, construction, and fire-resistive duct wrap of the existing grease ducts. Reference”: Section 107.2.1, IBC 2018.
3. Hood canopies shall extend at least 6” horizontally on all open sides beyond the edge of the top horizontal surface of the appliances under the hood. Note that the submitted hood canopy extends 48” from the back of the hood, not 62”. Reference: Section 507.4.1, IMC 2018.
4. Verify that adequate make-up air is being provided for the kitchen exhaust hood. Reference: Section 508.1 IMC 2018.
01/06/2026 Fire New Construction Standard REVIEW COMPLETED
12/16/2025 PDSD Application Completeness Express REVIEW COMPLETED