Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-1225-02217
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2026 | Site Zoning | APPROVED | Associated DP (TD-DEV-0125-00023) has been issued. | ||
| 02/11/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/05/2026 | Commercial Building | REQUIRES RESUBMIT | ACTIVITY NO. TC-BCA-0126-00007 ADDRESS: (780 W EL PUENTE LN TUCSON, AZ 85713) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. COMMENTS: 1. STRUCTURAL CALCULATIONS a. The structural calculations is not present on this set of submittals. b. Please submit. 2. UPLIFT CALCULATION a. Structural drawings illustrating how the solar panels are attached to the steel canopy are absent. a. Please provide these drawings. b. Provide structural calculation illustrating the resistance required to resist the lateral forces such as the uplift/wind at 115 mph at 3 second gust. a. Provide the mechanism to resist this such as what fastener used, what connectors used, etc. c. Please include the calculation within the structural calculation above. d. Please include the connector details within the structural drawings below. 3. STRUCTURAL DRAWINGS a. The structural drawings is not present on this set of submittals. b. Please submit. 4. SEAL/SIGNATURE/DATE a. Please ensure that all of the above documents are sealed/signed/dated by an Arizona licensed structural engineer. 5. Please resubmit. |
||
| 01/27/2026 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1225-02217 (3350 E GRANT RD TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov Electrical Review: 1. Provide a Grounding Electrode System at the detached structure per NEC 690.47. 2. Show the Grounding Conductor’s connection at the modules, mounting and metal support structure. 3. Show grounding details for the mounting equipment and metal support frame, NEC690.43. |
||
| 01/27/2026 | Outdoor Lighting | REQUIRES RESUBMIT | Outdoor lighting Review TC-COM-1225-02217 (3350 E GRANT RD TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. Clarify if there are any canopy lights being added. 2. Full cutoff lights under a canopy are exempt from lumens calculations, but must meet the 3,500K color temperature maximum limit. |
||
| 02/11/2026 | Site Engineering | REQUIRES RESUBMIT | Site Engineering Review TC-COM-1225-02217 3350 E GRANT RD Summary: Install 124KWDC Solar Shade Structure. Site Engineering comments are as follows: 1. Show the proposed height of the canopy. The PAAL side of the canopies shall be 15-ft or higher. A 1-ft set back from the PAAL would satisfy clearance requirements, as well. 2. The plan dimensions match the development package, however, the vehicle clearance must be shown for approval. To re-submit, visit the Tucson Development Center Online at: https://tdc-online.tucsonaz.gov/#/home The instructions for resubmittal can be found at: Revisions and Resubmittals Engineering Associate: Ryan Insalaco ryan.insalaco@tucsonaz.gov |
||
| 01/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |