Permit Number: TC-COM-1225-02188
Parcel: 13002003B

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02188
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2025 Water - PDSD Standard APPROVED
12/07/2025 Design Review Standard NOT REQUIRED Site not located within a Special District.
12/08/2025 Site Engineering Standard NOT REQUIRED
12/19/2025 Site Landscape Standard NOT REQUIRED
12/19/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/19/2025 Site Zoning Standard PENDING ASSIGNMENT
12/05/2025 Addressing Validation REQUIRES RESUBMIT Please ensure the permit number on the first page of construction plans matches the actual permit number and resubmit after other reviews are completed.

For questions, please contact Building_Official@tucsonaz.gov
12/18/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02188
ADDRESS: (3000 E 22nd ST Unit:111 Tucson, AZ 85713)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.


COMMENTS:
1. REFERENCE SITE PLAN File
a. The Reference Site Plan file shows THIS PROJECT Suite 111 (Barber Shop 951 sf).
b. The Building Permit Record address shows Suite 111.
c. However, the title block indicates this permit for Suite #121.
d. Please correct this discrepancy.
2. CONC FULL CD SET File, Sheet A-3
a. The Floor Plan shows the project as located on a different space South of the space mentioned in item #1 (Suite 111) above.
b. Space is labeled as NEW BEAUTY SHOP (FORMER BARBER SHOP) Suite 111.
c. However, per Pima Addressing Map and per Your REFERENCE SITE PLAN indicates this space to be Suite #121.
d. Which space are you revising?
e. Please correct his discrepancy.
3. FLOOR PLAN
a. Please show the entire layout such as the waiting area chairs, the cash counter, the beauty shop station chair allowing us to see the egress path of travel as well as able to verify the cash counter having the 34 inch high accessible counter, etc.
4. DRINKING FOUNTAIN
a. Ensure the water dispenser must be connected to a permanent supply of potable water.
b. Show the clear floor space for the cooler in compliance with Chapter 6 of ICC A117.1.
c. Ensure to install a permanently mounted disposable cup dispenser adjacent to the cooler mounted between 34” and 48” from finish floor complying to Chapter 3 of ICC A117.1.
5. Please resubmit.
Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
12/18/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Revise the ventilation calculations, identifying Suite 111 as a beauty salon. Footnote b on Table 403.3.1.1, IMC 2018 states that mechanical exhaust is required for the beauty salon and no air from the beauty salon may be recirculated to any other space. Heat pump, HP-1, serves the entire suite so the entire suite is to be considered a beauty salon. Reference: Section 403.2.1 (3), IMC 2018.
2. Revise the heating/cooling load calculations as needed to address the effect of the increased ventilation load on HP-1.
3. Verify that revised floor plan (i.e. showing the new walls) is used as a basis for the revised HVAC floor plan. Reference: Section 107.2.1, IBC 2018.
12/18/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Verify that revised floor plan (i.e. showing the new walls) is used as a basis for the revised plumbing floor plan. Reference: Section 107.2.1, IBC 2018.
2. The architect calls for the fire-damaged drinking fountain to be replaced with a point-of-use water dispenser. Revise the plumbing fixture specifications and the plumbing floor plan to reflect this change. Ensure that the installation of a permanently mounted disposable cup dispenser is included. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor. See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/2008-21_e_drinkingfountainpolicy.pdf.
12/18/2025 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
12/11/2025 Historic REVIEW COMPLETED Project not in any HPZ or National Register. Not in an archeological sensitivity zone. Based on these factors historic has no concerns at this time
Reviewed by Michael.Taku@tucsonaz.gov
12/05/2025 PDSD Application Completeness Express REVIEW COMPLETED