Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1225-02183
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/26/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. A cover sheet with code data/code analysis showing the following information. IBC 107.2.1 A. Provide the construction type of the building in the code data sheet. IBC 602.1 For example VB B. Provide the building’s occupancy classification. IBC 302.1 For example, B-Barber Shop C. Are fire sprinklers provided? Yes or No D. Are fire sprinklers required? Yes or No E. State the design occupant load of this building IBC 1004.1 F. Provide the Total square footage of the occupied space? 2. Please amend the plans to include a list of the year and name of the adopted applicable codes from the adopting ordinance. IBC 107.2.1 For example, 2018 International Building Code (IBC) 2018 International Residential Code (IRC) 2018 International Existing Building Code (IEBC) 2009 ICC A117.1 Accessibility Code (by reference) 2018 International Mechanical Code (IMC) 2018 International Plumbing Code (IPC) 2017 National Electrical Code (NEC) 2024 International Fire Code (IFC) 2018 International Fuel Gas (IFGC) 2018 International Energy Conservation Code (IECC) City of Tucson/Pima County Outdoor Lighting Code Local Amendments to Above Codes ( www.tucsonaz.gov/pdsd/building-codes ) 3. Please amend the plans to include a sheet index list that includes all the drawing sheets in this permit’s scope. IBC 107.2.1 4. Please amend the plans to provide a dimensioned floor plan with all spaces are labeled with a name or further description as needed to adequately convey the intended use and occupant load factor. IBC 302.1 & IBC 1004.5 Additionally, please show waiting area and sales counter. IBC 107.2.1 5. The existing and the proposed restroom do not appear to be accessible. Per IEBC Section 305.7, accessibility must be provided to the altered spaces. This includes the primary entrance, primary path of travel, sanitary facilities, drinking fountains, and signage. Please amend plans to show compliance with IEBC 305.7. For example, the toilet room does not appear to meet the clearance requirements of ICC A117.1-2009, Section 604.3. A. If the cost of providing or upgrading the items listed above to meet accessibility requirements is disproportionate to the overall cost of construction (i.e., exceeds 20% of the construction cost, excluding accessibility upgrades), please provide documentation to verify construction costs. If this exemption is used, accessibility improvements totaling at least 20% of the construction cost must still be provided. For example, if the project valuation is $40,000, then a minimum of $8,000 should be allocated toward accessibility upgrades. However, only the amount necessary to achieve full compliance is required to be spent. 6. Please amend the plans to show a landing outside the new exterior door at the same elevation on each side of the door. IBC 1010.1.4 & IBC 1010.1.5 for width and length. 7. Please amend the plans to provide a fastening schedule for the wall and roof sheathing, framing members, etc IBC 2304.10.2 Additionally, indicate this information on the wall assembly section details. 8. Please amend the plans to provide a complete wall assembly from footing to the top of the parapet. Include the exterior wall covering the parapet and down to the roof, providing flashing details as necessary. IBC 107.2.1 9. Please amend the plans to show the exterior walls provide the building with a weather-resistant exterior wall envelope. IBC 1402.2 For example, a weather-resistive exterior wall assembly: a water-resistive barrier installed over the building substrate; flashings at penetrations and terminations of the exterior wall finish; and a means of draining moisture that may penetrate behind the finish back to the exterior. 10. Please amend the plans to show foundation, slab, wall and roof connection details between the new and existing construction. IBC 107.2.1 11. Please provide the sealed structural calculations and construction drawings prepared by an Arizona licensed registrant used in the design of this addition with the next submittal. IBC 107.2.7 & IBC 1402.3 12. If required please provide the special inspection certificate with Part A, and Part B, completed with next submittal. IBC 107.2.1 https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf 13. If required please amend the plans to expand the statement of special inspections and print the complete statement on the construction documents. IBC 107.2.1 14 Please amend the plans to provide the R-value for batt and continuous insulation in the roof assembly with location. U-Factor, PF, and SHGC for fenestration. IECC C402.1, Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 12/18/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1225-02183 (5341 S 12TH AV TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). Electrical Review: Plans shall include (as necessary for scope of work), but may not be limited to items below: 1. Provide an electrical demo plan for any demo’ed electrical or appliances. 2. Provide electrical load calculations, for the Main Panels, Per NEC 220.40, demonstrating the existing electrical system can support the additional load. 3. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. 4. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. 5. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number. 6. Show all GFCI protection (NEC 210.8(B)) in readily accessible location per NEC 210.8. Additional comments may be forthcoming with complete electrical plans for the building and site. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 12/30/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1225-02183 ADDRESS/PARCEL: (5341 S 12TH AV TUCSON, AZ 85706) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. Provide complete plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2018. 2. Show that the shampoo sink faucets conform to section 412.10, IPC 2018. Shampoo sink faucets shall have hot water limited to a maximum temperature of 120 degrees Fahrenheit using a device conforming to ASSE 1070. |
||
| 12/31/2025 | Fire New Construction Standard | REQUIRES RESUBMIT | Resolve all building comments. john.vincent@tucsonaz.gov 5203495581 |
||
| 12/18/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-1225-02183 (5341 S 12TH AV TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf a. One new outdoor lighting fixture is being added. Please address the following comments. b. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3). c. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. d. Show lamps with a maximum of 3500K color temperature, OLC 402.1. e. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 12/19/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-1225-02183 Location: 5341 S 12TH AV Review Date: 12/19/2025 A Comment Response letter is required. Please address all reviewer’s comments in a separate document with all required documents for resubmittal. Site Engineering Comments: 1. The proposed addition of this commercial property requires the submission and approval of a Development Package. Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. 2. Site Engineering is unable to review and approve permit TC-COM-1225-02183 until an associated Development Package is reviewed and approved by all reviewers. 3. Updates to the site plan for submittal to the DP are needed follow the checklist provided: - The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf - The provided drawing of the existing building area/shape does not match that of the existing structure. - Show all existing lot features: covered patio, fenced in area, parking, trash containers, utility, and temporary structures. 4. Additional comments during DP submittal may be forthcoming. If you have any questions or concerns, please contact Dylan Molina. Dylan.Molina@tucsonaz.gov |
||
| 01/05/2026 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons Zoning Section Review PROJECT: TC-COM-1225-02183 5341 S. 12th Ave. Tucson, AZ 85706 10’ x 20’ building addition (1st Review) TRANSMITTAL DATE: 1/5/2026 This site is located in the C-2 zone (UDC 4.7.21). Personal Service is an allowed use in this zone subject to UDC Use Specific Standards 4.9.13.P. Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers. 2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 12/30/2025 | Water - PDSD Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1225-02183 ADDRESS/PARCEL: (5341 S 12TH AV TUCSON, AZ 85706) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. Please provide the water meter size and the total water demand to verify that it can accommodate the 3 new sinks and washer. Reference: IBC 2018, Section 107.2.1. |
||
| 12/09/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |