Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1225-02176
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/17/2025 | Commercial Electrical Standard | NOT REQUIRED | No Electrical or lights to be added under this permit. No modifications to the outdoor lighting. |
||
| 12/17/2025 | Outdoor Lighting Standard | NOT REQUIRED | No Electrical or lights to be added under this permit. No modifications to the outdoor lighting. |
||
| N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Commercial Building Standard | PENDING ASSIGNMENT | |||
| N/A | Commercial Mechanical Standard | PENDING ASSIGNMENT | |||
| N/A | Commercial Plumbing Standard | PENDING ASSIGNMENT | |||
| N/A | Fire New Construction Standard | PENDING ASSIGNMENT | |||
| N/A | Site Zoning Standard | PENDING ASSIGNMENT | |||
| N/A | Water - PDSD Standard | PENDING ASSIGNMENT | |||
| 12/08/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-1225-02176 Location: 1526 N ALVERNON WY Unit: BLDG 1 Review Date: 12/8/2025 Site Engineering Comments: 1. This site resides entirely in the City of Tucson Alvernon Wash Floodplain and will require that submission and approval of a floodplain use (FPU) permit for work within a floodplain. The FPU permit is a separate permit that can be submitted for within the "sub-records" tab of this associated building permit through TDC online. 2. For the submission of the FPU permit, provide all the same construction documents that were provided within this building permit submission 3. Final Site Engineering approval for permit (TC-COM-1225-02176) requires review and approval of associated submitted FPU permit. 4. It will be required that a dimensioned site plan be submitted showing the dimensions of the canopy compared to the drive through lane. This to review compliance with UDC 7.4.6.F.2 & UDC 7.4.6.E.2. It is required that the required the canopy either follow the required height clearance of 15 – feet or be setback one foot or greater from the drive through lane. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 12/05/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |