Permit Number: TC-COM-1225-02170
Parcel: 113075320

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02170
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2025 Site Zoning Standard APPROVED
12/05/2025 Site Engineering Standard NOT REQUIRED
12/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/22/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Provide the signed and sealed structural calculations, prepared by an Arizona licensed registrant, used in the design of this project. IBC 107.2.7
2. Please indicate any required special inspections for this project. For example, welding.
3. Please provide the ES report, manufacturer’s specifications for the liquid applied waterproof membrane used under the concrete topping slab and over the plywood sheathing, IBC 107.2.1 Additionally, please indicate special inspection is required and complete a special inspection form. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
4. Please amend the plan to show the method used to provide ventilation beneath balcony or elevated walking surfaces. IBC 2304.12.2.6 For example, Enclosed framing in exterior balconies and elevated walking surfaces that are exposed to rain, snow or drainage from irrigation shall be provided with openings that provide a net free cross-ventilation area not less than 1/150 of the area of each separate space.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
12/26/2025 Fire New Construction Standard REVIEW COMPLETED
12/04/2025 PDSD Application Completeness Express REVIEW COMPLETED