Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-1225-02167
Parcel: 12003137A

Address:
851 W AJO WY

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1225-02167
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/02/2025 Addressing Validation REQUIRES RESUBMIT Comment-Multiple building numbers and units need to be attached to address location. Each building requires separate permit. Units will have to be confirmed and assigned to Permit Application and on plan(s) prior to issuance. This project is for Building 1 please contact Pima County Addressing to verify address at Addressing@pima.gov or 520-724-9512. Please sign into your TDC account and request a change of address to this project to include building numbers and units and re-submit plan(s) with updated address to include building number with unit numbers.

If you have questions please contact me at Drew.Szentesy@tucsonaz.gov or contact the Building Official at Building_Official@tucsonaz.gov
12/02/2025 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1225-02167 (851 W AJO WY TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. The #8 Cu conductor to the new HVAC unit is undersized for the given 60A OCPD, NEC 240.4.
2. Provide a Service and service entrance equipment rated greater than the calculated load, NEC 408.30. The given load calculations exceed the rating of the service entrance bus.



Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov