Permit Number: TC-COM-1224-02438
Parcel: 10408005F

Address:
4755 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1224-02438
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2025 Commercial Electrical APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 1/10/2025 6:55:23 PM
01/14/2025 Commercial Mechanical APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 1/13/2025 9:30:20 AM
01/14/2025 Outdoor Lighting APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 1/10/2025 6:55:23 PM
01/24/2025 Site Zoning APPROVED
01/23/2025 Water - PDSD APPROVED
01/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/14/2025 Commercial Building REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 1/13/2025 2:22:02 PM
1. FIRM REGISTRATION: Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”. An active registration could not be found under the names "Haines Gipson & Associates" or "HGA" in the Arizona State Board of Technical Registration database: https://btr.az.gov/public/registered-firm-branch-search). Please confirm that the Engineer of Record has registered with the Board and update the title block to include a 5-digit Firm Registration number. For more information, see the following link: https://btr.az.gov/applicants/register-your-firmbranch
2. GENERAL - MECHANICAL UNITS: The HVAC Floor Plan, M1.0, and Mechanical Schedules, M2.0, reference new rooftop mechanical units each weighing between 900 and 2,900 lb. Please have the structural engineer of record
coordinate locations and weights of these Mechanical units and verify that the existing roof framing is sufficient to support the proposed loads. If reinforcement of the existing framing is required or if new framing is needed below the proposed units, please provide a structural detail.



Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 1/14/2025 11:27:48 AM
1. General: Provide the Special Inspections Intermediate Certificate. A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Part A & B need to be completed prior to Issuance. Part C
to be completed prior to final Inspection. (2018 IBC Chapter 17)
2. Sheet G1.0: The cover sheet does not include an architect’s seal. (2018 IBC section 107)
3. Sheets G1.2: Include the exit signs along the means of egress. Some exit signs are included but others are missing from the life safety plans. Coordinate the exit sign locations with the electrical plans. (2018 IBC section 1013)
4. Sheet A2.0: Include the counter, table, and seating accessibility details. (2009 ICC A117.1 sections 902, 904)
5. Sheet A5.0: Provide the fenestration U-Factors. (2018 IECC section C402)
01/14/2025 Commercial Plumbing REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 1/5/2025 11:03:25 PM
First Plumbing Review:
1). Plan Page P1.1: Coffee & Ice Makes can't share 1 backflow device. Add a separate backflow devices at ice maker & coffee machine. -2018 IPC 608.17.1.2
01/07/2025 Fire New Construction REVIEW COMPLETED
01/02/2025 PDSD Application Completeness Express REVIEW COMPLETED
01/27/2025 Site Engineering REVIEW COMPLETED